Specifications
8
Technical data
Connections
Ambient conditions
Mechanical data
48 | 54
Detector line and external alarm
indicators
●
Design
●
Conductor cross section
MC link
Operating temperature
Storage temperature
Air humidity
Protection categories (IEC 60529):
●
FDM223/FDM224,
in housing FDMH293-x
without seal DMZ1197-AD
●
FDM223/FDM224,
in housing FDMH297-R
without seal DMZ1197-AD
●
FDM223/FDM224,
in housing FDMH293-x
with seal DMZ1197-AD and metal
cable gland
●
FDM223H/FDM224H,
in housing FDMH292-R
without seal DMZ1197-AD
●
FDM223H/FDM224H,
in housing FDMH292-R
with seal FDMP223
●
FDM223H/FDM224H,
in housing FDMH292-R
with seal DMZ1197-AD and metal
cable gland
Environmental category according to
EN 54-11:
●
FDM223, FDM224
●
FDM223H, FDM224H
Electromagnetic compatibility:
●
80 MHz...3 GHz
Design according to EN 54-11:
●
FDM223, FDM223H
●
FDM224, FDM224H
Housing material:
●
FDM223/FDM224 in housing
FDMH293-x
●
FDM223/FDM224 in housing
FDMH292-R
●
FDM223H/FDM224H
Housing colors:
Spring clips
0.2...1.5 mm²
Proximity interface
-25...+70 °C
-30...+75 °C
≤95 % rel.
IP41
IP41
IP64
IP41
IP44
IP66
In buildings and outdoor areas
In buildings and outdoor areas
50 V/m
Type B (indirect activation)
Type A (direct activation)
Polycarbonate (PC)
Polycarbonate (PC)
Polyamide (PA)
007002_k_en_--