6.2 Checking function

007002_k_en_--
Manual call point FDM223
w
The manual call point is installed and electrically connected. See the chapter
'Installation [➙ 31]'.
1. Set the detector line to 'Test' on the control panel.
2. Push the keyhole cover to the right.
3. Open the door of the manual call point with the key.
4. Pull out the key.
5. Push the keyhole cover back into place.
6. Press the alarm button.
a
The alarm signal is transmitted.
7. Check whether an alarm is displayed on the fire control panel.
8. Push the black locking lever (1) at the top right of the switching unit to the right
until it clicks.
a
The alarm button is now protruding by approx. 5 mm.
9. Close the door of the manual call point.
a
The manual call point is ready for operation again.
10. Set the detector line to 'Normal operation' on the control panel.
a The detector line is ready for operation again.
Figure 20: Resetting manual call point FDM223
1
Locking lever
Commissioning
Checking function
1
6
39 | 54