Siemens FDM223 Technical Manual page 40

Manual call point
Hide thumbs Also See for FDM223:
Table of Contents

Advertisement

Commissioning
6
Checking function
40 | 54
Manual call point FDM224
w
The manual call point is installed and electrically connected. See the chapter
'Installation [➙ 31]'.
1. Set the detector line to 'Test' on the control panel.
2. Push the keyhole cover to the right.
3. Open the door of the manual call point with the key.
a
The alarm signal is transmitted.
4. Check whether an alarm is displayed on the fire control panel.
5. Pull out the key.
6. Push the keyhole cover back into place.
7. Close the door of the manual call point.
a
The manual call point is ready for operation again.
8. Set the detector line to 'Normal operation' on the control panel.
a The detector line is ready for operation again.