Bit = 0: Bumpless switchover is disabled. You can switch from local/manual mode to automatic
mode at any time.
Bit = 1: Bumpless switchover from local/manual mode to automatic mode is enabled. A
switchover from local/manual mode to automatic mode is only possible if the control settings of
the local/manual mode and automatic modes match. If switchover occurs at a different point in
time, this is indicated in the faceplate with the text "Switchover error".
Refer to the "Enable bumpless switchover to "Automatic" mode for operator only (Page 53)"
of the APL online help section for more on this.
A second feature bit is used to specify if bumpless switchover to automatic mode is only
possible via the faceplate or if switching is also possible via the interconnectable parameters
AutModLi and ManModLi (ModLiOp = 1).
Refer to the section "Enable bumpless switchover to "Automatic" mode for operator only
(Page 53)" of the APL online help section.
4.8

Activating the run time of feedback signals

Feature Bit
Number of the Feature bit: 11
Activating the run time of feedback signals
Use this Feature bit to activate the run time of feedback signals.
The default setting is 0.
Bit = 0: Deactivated: Tracking of feedback for simulation immediately after the trigger signal.
Bit = 1: Activated: Tracking of feedback for simulation after the trigger signal and expiration of
the monitoring time (MonTiDynamic). The feedback signals are generated after expiration of
the monitoring time.
4.9

Enable bumpless switchover to "Automatic" mode for operator only

Feature bit
Number of the Feature bit: 21
Enable bumpless switchover to automatic mode for operator only
You can use this Feature bit to specify whether bumpless switchover to automatic mode for
valves, motors and dosing unit should be enabled only if switching via the faceplate is in effect,
or whether switching using interconnectable inputs AutModLi and ManModLi (ModLiOp =
1) is also possible.
The default setting is 0
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
4.9 Enable bumpless switchover to "Automatic" mode for operator only