MULTI-TEC Wall-Mount Unit Control Board Terminals
Terminal
Rx+/Tx+
Rx-/Tx-
DI1
DI2
Dirty Filter Switch
DI3
High Pressure (CCM)
DI4
Low Pressure Switch
DI5
DI6
Damper Blade Switch
DI7
GND
Digital Ground
B1
Mixed Air Temperature Sensor
B2
Outdoor Air Temperature Sensor
B3
Return Air Temperature Sensor
B4
B5
Outdoor Humidity Sensor
B6
B7
Freeze Temperature Sensor
GND
Analog Ground
+VDC
24VDC to Outdoor Air Sensor
B8
Suction Temperature Sensor
B9
Suction Pressure Sensor
Y1
Y2
2-10VDC to Damper Actuator
Y3
GND
C1
NO1
NO2
NO3
C2
NO4
Stage 1 Heating
NO5
Stage 2 Heating
NO6
NO7
C7
NC7
C8
NO8
NO9
GO
24VAC Ground
G
TABLE 4
Function
Unit Disable
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Ground
24VAC+
Cool 1 Out
Not Used
Reheat Valve
24VAC+
Not Used
Blower 1
24VAC+
Not Used
Not Used
Blower 2
Blower 3
24VAC Hot
Type
Communication
Communication
Digital
Digital
Digital
Digital
Digital
Analog Input
10K Ohm Curve J
Analog Input
10K Ohm Type
Analog Input
10K Ohm Curve J
Analog Input
Analog Input
10K Ohm Curve J
Analog Input
10K Ohm Curve J
Analog Input
Power
Relay Output
Power
Relay Output
Relay Output
Relay Output
Relay Output
Relay Output
Form
N/C
N/C
N/C
N/C
N/C