Enthalpy Settings (Enthalpy Option); Limit Settings - Carrier CRECOMZR101A00 Installation Instructions Manual

Vertical/horizontal low leak/ultra low leak economizerone accessory for small rooftop units select 3 to 12.5 tons
Table of Contents

Advertisement

Table 6 — Enthalpy Manual Entry Setpoints for EconomizerONE Per Climate Zone
CLIMATE ZONES
a
2 TEMP OFF
1
65°F
2
65°F
3
65°F
4
65°F
5
70°F
6
70°F
7 & 8
75°F
CALIFORNIA
2 TEMP OFF
TITLE 24 ZONES
b
1
75°F
2
73°F
3
75°F
4
73°F
5
75°F
6
71°F
7
69°F
8
71°F
9
71°F
10
73°F
11
75°F
12
75°F
13
75°F
14
75°F
15
75°F
16
75°F
Controller Default
2 TEMP OFF
Settings
Default Set Points
63°F
NOTE(S):
a. See Fig. 19 for map of U.S. and Canada climate zones.
b. See Fig. 20 for map of California Title 24 zones
Economizers are shipped standard with an HH79NZ039 outside
air dry bulb sensor (see Fig. 25). System default setting (high temp
limit) is 63°F (17°C), and has a range of 48°F to 80°F (9°C to
27°C). Sensor is factory installed on economizer.
NOTE: A second HH79NZ039 sensor is provided for mixed air
temperature.
NOTE: California high temperature setting requirements by
region are shown in Table 7.

ENTHALPY SETTINGS (ENTHALPY OPTION)

If installing the optional HH57LW001 enthalpy sensor, then the
HH79NZ039 dry bulb outside air sensor must first be removed.
Wire sensor to harness 48TC005213 and the (5) wires from the
harness to the EconomizerONE harness in the return air chamber.
Harness 48TC005213 has a 5 pin plug that connects directly to the
HH57LW001 enthalpy sensor. See Fig. 19 for wiring connections.
Refer to Fig. 26 and Table 8.
California's
Title

Limit Settings

California's Title 24 code requires a high temperature limit setting
for all dry bulb outside air economizer changeover. The tempera-
tures vary by the region within California. See Table 7 for high
limit settings.
Lowest
RH%
Setting
22 Btu/lbm
43%
22 Btu/lbm
43%
22 Btu/lbm
43%
22 Btu/lbm
43%
22 Btu/lbm
28%
22 Btu/lbm
28%
22 Btu/lbm
19%
Lowest
RH%
Setting
22 Btu/lbm
19%
22 Btu/lbm
22%
22 Btu/lbm
19%
22 Btu/lbm
22%
22 Btu/lbm
19%
22 Btu/lbm
28%
22 Btu/lbm
32%
22 Btu/lbm
28%
22 Btu/lbm
28%
22 Btu/lbm
22%
22 Btu/lbm
19%
22 Btu/lbm
19%
22 Btu/lbm
19%
22 Btu/lbm
19%
22 Btu/lbm
19%
22 Btu/lbm
19%
24
High
Temperature
2 ENTH OFF
RH%
28 Btu/lbm
86%
28 Btu/lbm
86%
28 Btu/lbm
86%
28 Btu/lbm
86%
28 Btu/lbm
65%
28 Btu/lbm
65%
28 Btu/lbm
50%
2 ENTH OFF
RH%
28 Btu/lbm
50%
28 Btu/lbm
55%
28 Btu/lbm
55%
28 Btu/lbm
55%
28 Btu/lbm
50%
28 Btu/lbm
62%
28 Btu/lbm
68%
28 Btu/lbm
62%
28 Btu/lbm
62%
28 Btu/lbm
55%
28 Btu/lbm
50%
28 Btu/lbm
50%
28 Btu/lbm
50%
28 Btu/lbm
50%
28 Btu/lbm
50%
28 Btu/lbm
50%
2 ENTH OFF
28 Btu/lbm
94%
Table 7 — California Title 24 Regional High Limit Dry
Bulb Temperature Settings
CLIMATE
DEVICE TYPE
b
ZONES
1, 3, 5, 11-16
2, 4, 10
FIXED DRY
BULB
6, 8, 9
1, 3, 5, 11-16
2, 4, 10
DIFFERENTIAL
DRY BULB
6, 8, 9
FIXED
ENTHALPY
c
All
+ FIXED DRY
BULB
NOTE(S):
a. This table sourced from 2019 California Energy Code, Title 24, Part 6, Table
140.4-E Air Economizer High Limit Shut Off Control Requirements.
b. Only the high limit control devices listed are allowed to be used and at the set
points listed. Others such as Dew Point, Fixed Enthalpy, Electronic Enthalpy,
and Differential Enthalpy Controls, may not be used in any climate zone for
compliance with Section 140.4(e)1 unless approval for use is provided by the
Energy Commission Executive Director.
c. At altitudes substantially different than sea level, the Fixed Enthalpy limit value
shall be set to the enthalpy value at 75°F and 50% relative humidity. As an ex-
ample, at approximately 6,000 foot elevation, the fixed enthalpy limit is approx-
imately 30.7 Btu/lb
LEGEND
OAT —
Outdoor-air Thermostat
RA
Return Air
12
2THL
2EHL
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
2THL
2EHL
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
83°F
33 Btu/lbm
2THL
2EHL
83°F
33 Btu/lbm
a
REQUIRED HIGH LIMIT
(ECONOMIZER OFF WHEN):
DESCRIPTION
OAT exceeds 75°F
OAT exceeds 73°F
OAT exceeds 71°F
7
OAT exceeds 69°F
OAT exceeds
RA temperature
OAT exceeds return air temperature
–2°F
OAT exceeds return air temperature
–4°F
OAT exceeds return air temperature
7
–6°F
OAT exceeds 28 Btu/lb of dry air
OAT exceeds 75°F
RH%
48%
48%
48%
48%
48%
48%
48%
RH%
48%
48%
48%
48%
48%
48%
48%
48%
48%
48%
48%
48%
48%
48%
48%
48%
RH%
48%
b
or