PT2009-A1
PTO2006-A1
PT2008-A1
A6V10430571_en--_c
'Desk call station (RS485, 8+1)'
● Call station with 8 configurable, illuminated zone buttons plus talk button
● Buttons are freely operable
● Electret condenser microphone with gooseneck
● Monitored microphone
● Symmetrical audio transmission, analog
● RS485 data transmission ('PACE-Bus')
● Audio output 0 dB (line volume)
● Connection to control panel via CAT5 cable or above (max. 500 m) and
RJ45 connector
● Up to 5 call stations can be configured in a cascade 'daisy chain'
● Adapter module PTO2008-A1 for connection to the control panel
● Option to add up to three extension modules, each with 8 zone buttons
● Addressable via 8-way SIP switch in device
● Insertable labels for custom button identification
● Robust sheet steel housing
'Call station extension (RS485, 8)'
● Optional button extension for desk call station PT2009-A1
● Up to 3 button extensions possible for desk call station PT2009-A1,
offering a total of 32 buttons
● 8 configurable, illuminated zone buttons
● Insertable labels for custom button identification
'Desk call station (analog, 3+1)'*
● Call station with 3 configurable zone buttons plus talk button
● Buttons are freely operable.
● Electret condenser microphone with gooseneck
● Symmetrical audio transmission, analog
● Audio output 0 dB (line volume)
● Control signals for zones 1-3 and 'Talk'
● Connection to control panel via CAT5 cable or above (max. 150 m) and
RJ45 connector
● Supplied adapter module for connection to control panel
● Insertable labels for custom button identification
● Robust sheet steel housing
* The desk call station PT2008-A1' may only be used for standard applications
and not for alarm applications.
Operating elements in the system
Call stations
4
19 | 57