2 4 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump
Flaring tool
Figure 51
Piping Extension Beyond Flare Form
Flare dimension (B)
Pipe
Tightening
Gauge
torque
Min.
18-20N.m
Ø 6.4
8.4/0.33
(183-204kgf.cm)
25-26 N.m
Ø 9.5
13.2/0.52 13.5/0.53
(255-265 kgf.cm)
35-36 N.m
Ø 12.7
16.2/0.64 16.5/0.65
(357-367 kgf.cm)
45-47 N.m
Ø 15.9
19.2/0.76 19.7/0.78
(459-480 kgf.cm)
65-67 N.m
Ø 19.1
23.2/0.91 23.7/0.93
(663-683 kgf.cm)
75-85N.m
Ø 22
26.4/1.04 26.9/1.06
(765-867 kgf.cm)
Table 9
6.
Place fl aring tool onto the fl aring block.
7.
Turn the handle of the fl aring tool clockwise until the pipe is fully fl ared.
8.
Remove the fl aring tool and fl aring block, then inspect the end of the pipe
for cracks and even fl aring. Slide the nut up to see if the fl are is of proper
diameter and does not interfere with the threads in the fl are nut.
Data subject to change
A
Tube
(mm/inch)
Flare shape
Max.
8.7/0.34
90 ° ± 4
B
R0.4~0.8
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque or to
deform the piping in any way. You should fi rst connect the low-pressure (suction)
pipe, then the high-pressure pipe (liquid line).
Minimum Bend Radius
When bending connective refrigerant piping, the minimum bending
radius is 10cm (4in). See Figure 52.
Radius
Figure 52
Installation Manual
≥10cm (4in)