Step 7: Motor and drain pump maintenance
9k ~ 48k models (the rear ventilated model is used as an example)
Motor maintenance:
1.
Take out ventilation panel.
2.
Take out blower housing.
3.
Take out motor.
Figure 19
Pump maintenance:
1.
Remove four screws from the drain pump.
2.
Unplug the pump power supply and water level switch cable.
3.
Detach the pump.
Figure 20
Bosch Thermotechnology Corp. | 05.2019
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump | 15
Motor
Blower housing
Ventilation panel
Pump
60k model
Motor maintenance (there are three methods):
Method 1 - Access from top
1.
Remove the top cover as shown.
Figure 21
2.
Loosen the four bolts and two screws on the front plate.
Figure 22
3.
Remove the motor cord, take off the front side plate and repair the motor.
Figure 23
Method 2 - Access from bottom
1.
Remove the bottom base cover as shown.
Figure 24