1 8 | Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump
Drainage test (
9k ~ 48k models)
Check that the drainpipe is unobstructed.
This test should be performed on newly built houses before the ceiling is fi nished.
Units without a pump
1.
Fill the water pan with 2 liters of water.
Stow tube
Figure 34
2.
Check that the drainpipe is unobstructed.
Units with a pump
1.
Remove the test cover.
Test cap
Figure 35
2.
Fill the water pan with 2 liters of water.
Data subject to change
Figure 36
3.
Turn on the unit in COOLING mode. You will hear the drain pump. Check
whether the water is discharged properly (a 1-minute lag is possible,
depending on the length of the drain pipe), Check whether water leaks from
the joints.
4.
Turn off the air conditioner and put the cap back on.
Drainage test (
60k model)
Units without a pump
1.
Fill the water pan with 2 liters of water.
Figure 37
2.
Check that the drainpipe is unobstructed.
Installation Manual
Stow tube
Stow tube