Note 1) Required condition
Classification
First branch joint ~
Farthest Indoor unit
Total length of
extended pipe
Each Y-joint ~ Each
indoor unit
Difference between the distance of the outdoor unit to the
farthest indoor unit and nearest indoor unit ≤ 45 m
(a+b+c+d+e+f+g+p)-(a+h) ≤ 45 m
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 40m, but when the
indoor unit is located at lower level than outdoor unit, allowable height difference is 50 m.
※ Total refrigerant amount of the system must be less than 100kg. If total refrigerant amount of system is over than 100kg, the
system has to be divided into smaller system, each less than 100kg.
Installing the branch joint between outdoor units
Installation of outdoor joints
Low pressure gas pipe
High pressure gas pipe
※ For HR System, connect liquid pipe, high pressure gas pipe and low pressure gas pipe.
※ For H/P System, connect liquid pipe and high pressure gas pipe.
Condition
45 m ≤ b+c+d+e+f+g+p ≤ 90 m: Size of
the branch pipe (b, c, d, e, f, g) must be
increased by one grade
If the size of the main pipe (pipe that
connects between the outdoor unit ~
first branch joint) was not increased
by one grade: a+(b+c+d+e+f+g)×2
+h+i+j+k+l+m+n+p ≤ 500 m
If the size of the main pipe (pipe that
connects between the outdoor unit ~ first
branch joint) was increased by one grade:
(a+b+c+d+e+f+g)×2 +h+i+j+k+l+m+n+p ≤
500 m
h, i, j, ... p ≤ 45 m
Liquid pipe
Branch joint between outdoor units
must not be installed in vertical position.