Samsung DVM S Water AM080FXWANR Technical Data Book page 47

Vrf, r410a, 50/60hz, hp/hr premium energy efficiency type, premium compact type
Hide thumbs Also See for DVM S Water AM080FXWANR:
Table of Contents

Advertisement

10. Installation
7. When installing multiple outdoor units at the same place, construct a H beam or an anti-vibration frame on the base
ground to install the outdoor unit.
8. After installing a H beam or an anti-vibration frame, apply corrosion protection and other necessary coating.
9. When concrete construction for outdoor unit installation is completed, install an anti-vibration pad (t=20 mm or
more) or an anti-vibration frame to prevent vibration of the outdoor unit from transferring to the base ground.
10. Place the outdoor unit on a H beam or an anti-vibration frame and fix it with the bolt, nut and washer. (The bearing
force has to be over 3.5 kN)
Foundation
150mm or more
Ditch
Outdoor unit installation
Foundation
(or H beam or anti vibration
frame)
Fixing the outdoor unit
A
Hole on outdoor unit for fixing anchor bolt (4 - Ø12)
B
Base ground (H-beam or anti-vibration frame)
Classification
Models
A
B
C
D
※ For adding the anti-vibration frame on the base ground, the specification for the fixing hole depends on the
specification of the anti-vibration frame.
Base ground
AM080/100/120FXWATT
Outdoor unit
Anchor bolt
20 mm
Nut, Spring
Anti-vibration pad
washer
A
Foundation (or H beam or anti
vibration frame)
Over A + 10~20 mm
Small type
770
656
523
550
Large type
AM200FXWATT / AM300KXWATT
1100
995
515
550
(Unit : mm)