10. Installation
Connecting the power terminal
▶ Connect the cables to the terminal board with solderless ring terminals.
▶ Properly connect the cables by using certified and rated cables and make sure to fix them properly so that external
force is not applied to the terminal.
▶ Use a driver and wrench that can apply the rated torque when tightening the screws on the terminal board.
▶ Tighten the terminal screws by complying rated torque value. If the terminal is loose, fire can occur due to arc heat
generation and if the terminal is too tight, terminal board could get damaged.
(field supply)
Conduit mounting plate
Screw
M4
M8
ꞏ When removing the outer sheath of the power supply cable, be careful not to scratch the inner sheath of the cable.
CAUTION
ꞏ Make sure that more than 20mm of the outer sheath of the indoor unit power and communication cable are
inside the electrical component box.
ꞏ Install the communication cable separately from power cable and other communication cables.
Communication cable
(Indoor/Outdoor unit)
External power
supply / External
contact signal
Sub unit 3 phase
(380-415 V)
(Knock out hole)
Protection tube for power cable
Lock nut
Conduit
(field supply)
1.2~1.8
5.5~7.3
3 phase
380-415 V
MCCB+
ELB
or
ELCB
Tightening torque for terminal (N∙m)
Single phase (220-240 V) power cable
3 phase (380-415 V) power cable