Viessmann VITOCELL 100-V Installation And Service Instructions Manual page 10

Heating water buffer cylinder
Table of Contents

Advertisement

Installation sequence
Fitting the cylinder temperature sensor and thermometer sensor (if supplied)
4.
1.
2.
Fig. 6
Recess for thermometer cable
A
Note
The cylinder temperature sensor is supplied in the control unit pack.
01. Insert the cylinder temperature sensor as far as it
will go into the opening of the clamping device.
02. Hand-tighten the cylinder temperature sensor with
the screw provided.
Note
Hold the cylinder temperature sensor in place in
the sensor terminal until the screw is screwed in.
!
Please note
Overtightening the fixing screw may dam-
age the cylinder temperature sensor.
Torque: Max. 2 Nm
03. Remove the top cover.
04. Clamp the thermometer sensor in the clamping
bracket.
05. Guide the thermometer cable through the groove
in the thermal insulation and the hole in the sheet
steel casing.
10
3.
5.
6.
7.
A
06. Secure the thermometer (accessory) to the wall.
Installation instructions for wall thermometer
07. Refit the top cover.
Note
The recess
A
in the top cover is intended for the
thermometer cable.
08. For heating water flow temperatures in excess of
95
C, remove the pipe collars from the pipe out-
º
lets (pipe collars have l.h. threads).
09. If no immersion heater is being installed, seal the
front female connection with the plug supplied and
fit the cover.
10. Affix supplied type plate to the back of the cylin-
der.