Bosch 120 Series Product Information page 9

Glt non-automatic fire detector

Advertisement

Produktinformation FMC−120−DKM / EST GLT
6. Functional description
6.1. Manual call point
Manual call point and stop device: In the event of an alarm, the glass pane (2) is broken
first, then the manual call point (3) is pressed hard.
This activates the microswitch for alarm triggering and the display LED (4) flashes.
A locking mechanism holds the pressed push button down.
The pressed push button is reset by manually activating the reset lever (5) or by opening
the detector door (1) ⇒ The alarm is reset and the display LED goes out (4).
1
2
3
6.2. Functional test
Manual call point and stop device: To trigger the alarm, press the manual call point (3)
hard. The display LED (4) flashes. Use the reset lever (5) to return the manual call point to
the starting status.
6.3. Test detector
A maximum of 1 test detector (1) may be connected to the electrical end of the primary
line. Up to 30 automatic fire detectors may be connected to the primary line to be tested.
The test detector is supplied by the fire panel.
1
4
max. 30
Page 9 of 18
5
3
3
2
PI − 34.51 en
1
2
1
BMZ
BDL−F.01U.066.178
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib