Setting Procedure

1. Cross Fault Detection (G9SX-NSA222-T03-@)
Set the cross fault detection mode for safety inputs by shorting Y1
to 24 V or leaving it open. When cross fault detection is set to ON,
short-circuit failures are detected between safety inputs T11-T12
and T21-22. When a cross fault is detected, the following will
occur.
(1) The safety outputs and logical AND outputs lock out.
(2) The LED error indicator is lit.
(3) The error output (auxiliary output) turns ON.
Cross fault
detection
OFF
Corresponds to
Safety Category 2
Corresponds to
Safety Category 3
ON
Corresponds to
Safety Category 3
(Cross fault
detecting mode
(for safety inputs)).
2. Reset Mode (G9SX-NS202-@/NSA222-T03-@)
Set the reset mode using feedback/reset input terminals T31,
T32, and T33.
Auto reset mode is selected when terminal T32 is shorted to 24 V
and manual reset mode is selected when terminal T33 is shorted
to 24 V.
Auto reset mode
KM1
KM2
KM3
KM4
+24 V
KM5
T31
T32
T33
22
Compact Non-Contact Door Switch
Wiring
+24 V
+24 V
T11
T12
T21
T22
Y1
+24 V
+24 V
+24 V
T11
T12
T21
T22
Y1
T11
T12
T21
T22
Y1
Manual reset mode
KM1
Reset
KM2
switch
KM3
KM4
+24 V
KM5
T31
T32
T33
D40A/
3. Setting Logical AND Connection (G9SX-NS202-@/
NSA222-T03-@)
When connecting two or more Non-contact Door Switch
Controllers by logical AND connection, set the logical AND
connection preset switch on the Controller that is on the input side
(Unit B in the following diagram) to AND.
Unit A
L1
T41
Unit B
Note: A setting error will occur and Unit B will lock out if the logical
AND setting switch on the Unit is set to OFF.
4. Setting the OFF-delay Time (G9SX-NSA222-T03-@)
The OFF-delay preset time on G9SX-NSA222-T03-@ is set from
the OFF-delay time preset switch (1 each on the front and back of
the Unit).
Normal operation will only occur if both switches are identically
set.
An error will occur if the switches are not identically set.
Front
Switch
Refer to the following illustration for details on setting switch
positions.
G9SX-NSA222-T03-@
0.9
0.8
1.0
0.7
1.2
0.6
1.4
0.5
1.8
0.4
2.0
0.3
2.5
0.2
3.0
0
OFF-DELAY
Notch
Example 1: 0-second
G9SX-NS
Flexible Safety Unit
AND
A2
OFF
AND
T42
OFF
Back
Switch
0.9
0.8
1.0
0.7
1.2
0.6
1.4
0.5
1.8
0.4
2.0
0.3
2.5
0.2
3.0
0
OFF-DELAY
Example 2: 0.8-second