Table 1B Electrical Specifications - Bard QW2S3DA Installation Instructions Manual

Geothermal r-410a staged capacity packaged heat pump
Hide thumbs Also See for QW2S3DA:
Table of Contents

Advertisement

RATED VOLTS,
Model
Hz & PHASE
QW2S3DA0Z
230/208-60-1
QW2S3DB0Z
230/208-60-3
QW2S3DC0Z
460-60-3
QW3S3DA0Z
230/208-60-1
QW3S3DB0Z
230/208-60-3
QW3S3DC0Z
460-60-3
QW4S3DA0Z
230/208-60-1
QW4S3DB0Z
230/208-60-3
QW4S3DC0Z
460-60-3
QW5S3DA0Z
230/208-60-1
QW5S3DB0Z
230/208-60-3
QW5S3DC0Z
460-60-3
 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
l Based on 75ºC copper wire. All wiring must conform to the National Electric Code and all local codes.
TABLE 1B
Electrical Specifications
MINIMUM
NO. FIELD
CIRCUIT
POWER
AMPACITY
CIRCUITS
1
20
1
14
1
9
1
27
1
22
1
13
1
37
1
28
1
17
1
43
1
30
1
15
MAXIMUM
EXTERNAL FUSE
FIELD POWER
OR CIRCUIT
WIRE SIZE
BREAKER
l
30
10
20
12
15
14
40
8
30
10
15
14
50
8
35
8
20
12
60
8
40
8
20
10
GROUND
WIRE SIZE
l
10
12
14
10
10
14
10
10
12
10
10
10
Manual 2100-738C