RATED VOLTS,
Model
Hz & PHASE
QW2S3DA0Z
230/208-60-1
QW2S3DB0Z
230/208-60-3
QW2S3DC0Z
460-60-3
QW3S3DA0Z
230/208-60-1
QW3S3DB0Z
230/208-60-3
QW3S3DC0Z
460-60-3
QW4S3DA0Z
230/208-60-1
QW4S3DB0Z
230/208-60-3
QW4S3DC0Z
460-60-3
QW5S3DA0Z
230/208-60-1
QW5S3DB0Z
230/208-60-3
QW5S3DC0Z
460-60-3
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
l Based on 75ºC copper wire. All wiring must conform to the National Electric Code and all local codes.
TABLE 1B
Electrical Specifications
MINIMUM
NO. FIELD
CIRCUIT
POWER
AMPACITY
CIRCUITS
1
20
1
14
1
9
1
27
1
22
1
13
1
37
1
28
1
17
1
43
1
30
1
15
MAXIMUM
EXTERNAL FUSE
FIELD POWER
OR CIRCUIT
WIRE SIZE
BREAKER
l
30
10
20
12
15
14
40
8
30
10
15
14
50
8
35
8
20
12
60
8
40
8
20
10
GROUND
WIRE SIZE
l
10
12
14
10
10
14
10
10
12
10
10
10
Manual 2100-738C