Operating Limits - York D4IC-360 Technical Information

Rooftop air conditioners
Table of Contents

Advertisement

CAUTION
When connecting the power supply and control wiring to the unit,
waterproof type wires must be used to avoid water or humidity
getting into the unit during normal operation. These waterproof
conditions also apply when a switch is installed at job site.
See Fig. 8 for typical wiring on job site.
NOTES:
1. All job site wiring should be carried out in compliance with
all city and local standards and/or regulations in force at
the time of installing the unit.
2. Should it be necessary to remove any cables supplied
with the unit, these should be replaced by cables of the
HO5V-K, HO7V-K or equivalent type, and be numbered
clearly for identification purposes.
. Motors are intrinsically protected, except for the indoor
fan motor, which has external protection.
4. This unit is wired for operation with a 415 V power sup-
ply.
5. See the Identification Plate for the maximum size of the
automatic switch and minimum power supply cable sec-
tion.
6. All motors are factory wired to rotate in the correct direc-
tion.
Thermostat
The ambient thermostat should be located on an inner
wall, at about 1.5 m. above floor level, where it will not be
exposed to air flows, direct sunlight or heat from other elec-
tric devices. For general installation, follow the instructions
supplied by the manufacturer. To connect the thermostat to
the unit, shielded colour-coded 10 x 0.22 mm² wires should
be used.

7 - Operating limits

D4IC/D4IG
Cool
Heat
B4IH
pump
D4IG
Gas heating
DB: Dry bulb temperature. WB: Wet bulb temperature.
16
Voltage limits
Indoor coil entering air temp.
Outdoor temp.
Indoor coil entering air temp.
Summer
cycle
Outdoor temp.
Indoor coil entering air temp.
Winter
cycle
Outdoor temp.
Outdoor temp.
Typical job site wiring
CONTROL WIRING
COOLING/HEATING (DPC-1 24 VAC ELECTRONIC
THERMOSTAT))
CONNECTING
STRIP
R
B
G
Y1
Y2
O/B
W
AL
X1
X2
POWER SUPPLY WIRING
CONNECTIONS
FOR POWER
SUPPLY
GROUNDING
TERMINAL
Min./Max.
WB°C Min./Max.
DB°C Min./Max.
DB°C Min./Max.
WB°C Min./Max.
DB°C Min./Max.
DB°C Min./Max.
DB°C Min./Max.
DB°C Min./Max.
DB °C Min./Max.
AUTO
PROG
AUTO
��
4
0h 2
4
6
8 10 12 14 16 18 20 22 24
����
����
DPC-1
THERMOSTAT
R
B
G
Y1
Y2
O/B
W
AL
X1
X2
SHIELDED
CABLE
10 x 0,22 mm
2
L1
SEE WIRING
L2
SPECIFICATIONS TABLE
FOR POWER SUPPLY
L3
CABLE AND SWITCH
SIZING
N
PE
- Fig. 8 -