4 Installation
4.3
Connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
4.3.1
About electrical compliance
Equipment  complying  with  EN/IEC  61000­3­12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low­voltage
systems with input current >16 A and ≤75 A per phase.).
4.3.2
To connect the electrical wiring on the
option box
1 Insert the wiring from the bottom of the option box.
2 Make sure the low voltage wiring is located on the right. Route it
through the intake hole and fasten it with cable ties:
c
b
a
a
Low voltage wiring
b
High voltage wiring
c
Main power supply
NOTICE
The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 25 mm.
4.3.3
To connect the option box power supply
1 Connect option box terminal X1M to control box terminal X1M.
X2M
A4P
A4P
X1M
X1M
1
2
3
1
X8M
1
GND
2
L
3
N
2 Fix  the  cable  with  cable  ties  to  the  cable  tie  mountings  to
ensure strain relief and to make sure that it does NOT come in
contact with sharp edges.
Installation manual
4
X2M
2
3
X8M
CAUTION
Do NOT push or place redundant cable length in the unit.
4.3.4
To connect the interconnection cable
between option box and control box
1 Connect the connectors from the accessory bag to X5A on A1P
of both the control box and the option box PCB.
2 Connect the connectors by way of a field­supplied cable.
a
X5A
A4P
a
Connectors (accessory)
b
Interconnection cable (field supply)
4.3.5
To connect the electrical meters
INFORMATION
In case of an electrical meter with transistor output, check
the  polarity.  The  positive  polarity  MUST  be  connected  to
X2M/7  and  X2M/9;  the  negative  polarity  to  X2M/8  and
X2M/10.
1 Connect the electrical meters cable to the appropriate terminals
as shown in the illustration below.
X2M
A4P
10
9
8
7
X1M
X8M
S5P S6P
2 Fix the cable with cable ties to the cable tie mountings.
Daikin Altherma low temperature monobloc option box
b
a
X5A
A4P
EK2CB07CAV3
4P405546­1 – 2015.03