INSTALLATION MANUAL
Multi-zoning base unit 230 V
1
Scope of supply
1x
2
About these instructions
These instructions must be read completely and thoroughly before commencing
any work with the base. These instructions must be kept and are to be handed
over to future users.
https://qr.daikin.eu?N=EKWUFHTA1V3
The following symbols show
a warning with respect to electrical voltage
important information.
3
Safety
3.1 Intended use
The base serves
the arrangement of a room-by-room temperature control system with a
maximum of 10 zones for heating and cooling systems,
the connection of a maximum of 18 actuators and 10 room control units,
the connection of actuators with the direction of control action NC (normally
closed) or NO (normally open), depending on the thermostat used,
the connection of an external timer,
depending on the type used, the connection of a pump or a boiler, a CO
signal generator, a temperature limiter or dew point sensor,
a fixed installation.
Every other use, modification and conversion is expressly forbidden and leads to
dangers the manufacturer cannot be held liable for.
3.2 Safety notes
All safety notes in these instructions must be observed in order to avoid acci-
dents involving personal harm and/or property damage.
WARNING
Danger to life due to the electrical voltage at the base station!
Always disconnect from the mains network and secure against unintended
activation before opening.
Only an authorised electrician may open the device.
Disconnect external voltages and secure against activation.
Only use the product if it is in perfect state.
Do not operate the device without the device cover.
This unit is not intended to be used by persons (including children) with restrict-
ed physical, sensory or mental skills or those who lack experience or knowl-
edge. If necessary, these persons must be supervised by a person responsible
for their safety or receive instructions from this person on how to use this unit.
Ensure that children do not play with this device. Children must be super-
vised if necessary.
In case of emergency, disconnect the complete room-by-room temperature
control system.
3.3 Personnel-related preconditions
The electrical installation must be performed according to the current national
regulations as well as according to the regulations of your local electric power
utility company. These instructions presume specialist knowledge corresponding
to an officially recognised degree in one of the following professions:
Systems Mechanic for sanitary, heating and air condition technology
Electrical Equipment Installer or
Electronics Engineer
according to the profession designations officially announced in the Federal Re-
public of Germany, and to comparable professions within the European Com-
munity Law.
2x
T4AH
4

Device overview

4.1 Connections and indications
The following instructions show the full equipment. Individual positions may be
omitted depending on the present base.
1
2
3
4
5
6
7
14
13
1 Boiler connection
2 Pump connection
3 Protective conductor connection
(only for 230 V)
4 Voltage supply
5 Fuse
6 Temperature limiter or dew point
sensor
7 Reduction channel, external timer
4.2 Technical data
Operating voltage:
Power input 230 V:
Fuse 230 V:
Number of heating zones:
Connectable actuators Type
10 heating zones:
The following applies to other actuators than those mentioned above
Inrush current per actuator:
Pump/boiler control
Switching power:
Turn-on delay:
Follow-up time fixed/adjustable: 2 min / 5 - 15 min
Pump protection function:
Control direction:
Ambient temperature:
Storage temperature:
Ambient humidity:
Temperature for ball pressure test: Terminals: 100 °C
Pollution degree:
Rated impulse voltage:
ERP class acc. to EU 811/2013: 1=1 %
Protection class 230 V:
Protection type:
Type action:
Dimensions (H x L x D):
4.3 Conformity
This product is labelled with the CE Marking and thus is in compliance with
following regulations:
2014/30/EU with amendments "Council Directive on the approximation of the
laws of the Member States relating to Electromagnetic Compatibility"
2014/35/EU with amendments "Council for Coordination of the Regulations
of EU Member Countries regarding the electrical equipment for use within
certain voltage limits"
2011/65/EU "Restriction of the Use of Certain Hazardous Substances in
Electrical and Electronic Equipment"
Increased protection requirements may exist for the overall installation, the com-
pliance of which is the responsibility of the installer.
EKWUFHTA1V3
8
9
10
12
11
8 Heating/cooling change-over
9 Thermostat connection
10 LEDs
11 Strain relief
12 Connection of actuators
13 DIP switch
14 Contacts for casing cover with
integrated system clock
230 V ±10 %, 50 Hz
max. 50 VA
T4AH
10
EKWCVATR1V3
max. 18
max. 500 mA (for 230 V)
2 A, 200 VA inductive
2 min
14 days for 1 minute
NC or NO
0 to +50 °C
-20 to +70 °C
80%, not condensing
Plastic enclosures: 75 °C
2
1500 V
II
IP 20
Type 1 / Type 1.C
90 x 326.5 x 50 mm
1

Advertisement

loading

Summary of Contents for Daikin EKWUFHTA1V3

  • Page 1: Device Overview

    INSTALLATION MANUAL EKWUFHTA1V3 Multi-zoning base unit 230 V Scope of supply Device overview 4.1 Connections and indications The following instructions show the full equipment. Individual positions may be omitted depending on the present base. T4AH About these instructions These instructions must be read completely and thoroughly before commencing any work with the base.
  • Page 2 Installation LED signalling Function Colour Explanation Pump/boiler Green On: Pump/boiler active Off: Pump/boiler inactive Flashing: Temperature limiter/dew point sensor active Mains voltage Green On: Device in operation Off: Device not in operation Flashing: Valve protection function active (Option) Fuse On: Fuse defective Change over Blue On: Cooling mode active...