Installing the CCU

Location for Central Control Unit (CCU)

The CCU is intended for installation in a residential or office-type environment. It needs to be mounted at a
convenient working height on a dry flat wall. The normal height is 1 metre from the floor to the bottom of
the CCU case.
CAUTION
Do not site the CCU where it will be subjected to excessive levels of heat, dust damp or high humidity.
Locating the equipment near sources of electromagnetic radiation such as heavy electrical switch-gear, lift
machinery or electric arc welders should be specifically avoided.
Allow at least 100 mm of free space all around the CCU for ventilation and 310 mm to the right or
underneath the CCU for the addition of the Battery Back Up unit.
The CCU needs to be within approximately two meters, of a dedicated mains power supply outlet. The CCU
must not share the same mains supply socket with any other electrical appliance.

Mounting the CCU

When a suitable location has been found, mark the screw locations on the mounting surface using the
mounting bracket provided.
If the CCU is being mounted on masonry or plasterboard, suitable wall plugs must be used. Drill and plug
four holes in the wall at the marked locations. The holes should be deep enough to accept a 2.5cm screw.

CCU Mounting bracket

The main unit is mounted on a wall using the bracket supplied and should have top and side clearance as
shown.
125 mm
Clearance
280 mm
145 mm
54
Clearance
mm
145 mm
Clearance
450 mm
Clearance
Page 8