Side Wall Termination Assembly - Vermont Castings SDDVT Homeowner's Installation And Operating Manual

Stardance direct vent/natural vent gas heater
Table of Contents

Advertisement

1/4-20 x
3/8 Phillips
Screws
Fig. 21 Simpson Dura-Vent - install inner adapter pipe.
ST355b
dura vent
attach inner assy
no restrictor plate
6/07 djt
Fig. 22 Simpson Dura-Vent - install outer adapter pipe.
Install Vent Adapter Pipe
(Selkirk Corporation Vent Components)
The appliance adapter (AA) adapts DIRECT-TEMP to
most direct vent appliances incorporating outlet col-
ST356
lars configured to receive most common 4" (ID) by 6⁵⁄₈"
(OD) or 5" (ID) by 8" (OD) "Twist Lock" style, direct vent
dura vent
systems.
attach outer assy
The adapter incorporates two indentations on the outer
4/7/00 djt
wall of the inlet end, which are designed to "Twist Lock"
into place upon attachment to the appliance outlet. Align
the adapter indentations with the entry slots of the appli-
ance outlet and slide together. Turn the adapter clock-
wise approximately one-quarter turn to lock in place.
The outlet end of the adapter is standard DIRECT-
TEMP construction.
For connection of Direct-Temp to units with 4" x 7" flue
outlets, the following methods have been approved:
Install the Universal/Napoleon Appliance Adapter
4DT-AAN.
Connect a standard Direct-Temp pipe length (do
not use an adjustable length in this application) a
minimum of 1¹⁄₂" over the flue outlet. The outside of
the Direct-Temp Length will fit inside the flue outlet
20012734
Inner Adapter
Pipe
ST355b
ST356a
Stardance Direct Vent/Natural Vent Gas Heater
Secure with a minimum of two #8 x 1/4" sheet metal
screws and seal with hi-temp silicone.
For units factory equipped with appliance adapters from
other brands of Direct Vent systems, it is permissible
to simply slide a length of DT pipe over the appliance
adapter. Secure with a minimum of two #8 x 1/4" sheet
metal screws and seal with hi-temp silicone.

Side Wall Termination Assembly

1. Locate the vent opening on the wall. Refer to Page
7, Figure 6, to determine the opening centerline.
It may be necessary to first position the stove and
measure to find the hole location. Depending on
whether the wall is made of combustible materials,
cut the opening to the size shown in Figure 24. Com-
bustible wall openings must be framed as shown in
Figure 23.
CFM System
9³⁄₈"
(240mm)
9³⁄₈"
(240mm)
Combustible Wall
10"
DuraVent
(254 mm)
System
VO584-100
Fig. 23 Locate vent opening.
2. Measure the wall thickness and cut the wall sleeve
sections to proper length (MAXIMUM 12"). Assemble
the sleeve with the #8 sheet metal screws supplied.
Attach the firestop plate to the sleeve end with the
holes. (Fig. 24) NOTE: The wall sleeve is required
VO584-100
in combustible walls only.
Vent Opening
3. Install the Wall Firestop/Sleeve assembly into the
2/99 djt
wall cutout and fasten the firestop to the wall cutout
framing members. (Fig. 24)
For DuraVent pipe only: Install vent pipe by aligning
the locking system together, sliding the pipes togeth-
er and twisting clockwise.
• Install 90° elbow. Twist lock as before.
• Slide the wall plate over horizontal run before at-
taching the horizontal run to the elbow. Fasten wall
plate to wall.
4. For CFM Vent Pipe only: If necessary, measure
to determine the vertical length (X) of pipe required
from the adapter pipe to the wall cutout centerline,
Framing Detail
7¹⁄₂"
(191 mm)
Noncombustible Wall
17