Vermont Castings 2310 Homeowner's Installation And Operating Instructions Manual page 9

Vermont castings coal stove homeowner's installation and operating instructions 2310

Advertisement

Prefabricated
Chimney
Single-wall
Chimney Connector
Chimney
Connector
Heat Shield
VIGILANT
Bottom
Heat
Shield
Fig. 9 Chimney connector heat shields may be used to re-
duce clearances when single-wall connectors are used.
Clearances With Double Wall Chimney
Connectors And Rear Stove Heat Shields
ST687
chimney connector
When a rear heat shield is used on the stove and a
8/7/01 djt
double wall chimney connector is used, the rear clear-
ance is 15¹⁄₂" (395 mm) and the chimney connector
clearance is 12" (300 mm).
Clearances With Single-wall Chimney
Connectors, Connector Shields And Rear
Stove Heat Shields
Use of both stove and chimney connector heat shields,
on single-wall connectors, in top-exiting installations
reduces the required clearance. (Fig. 10)
Fig. 10 Minimum clearance, chimney connector heat shield,
rear heat shield.
ST688
Vigilant
clearances
parallel,
2000898
rear heat shield,
chimney connector
heat shield
8/7/01 djt
24"
(610mm)
Max.
ST687
13" (330mm)
18"
(460mm)
ST688
Protected Walls
A properly constructed wall shield may be used to
change an unprotected wall to a protected wall, allow-
ing the clearances given in the right half of the Clear-
ance Chart.
Wall shields should be
constructed of 24 gauge
or heavier sheetmetal,
1/2" noncombustible insu-
lation board, or common
brick laid on flat (3¹⁄₂" side
down). Shields must be
spaced out from the com-
bustible wall or ceiling 1"
on noncombustible spac-
ers. The spacers should
not be directly behind the
stove or chimney connec-
tor.
Air must be able to flow
between the wall and the
shield. At least one-half
(50%) of the bottom 1"
of the shield should be
open and the shield must
stop 1" from the ceiling.
Protect the top opening
with metal screening to
prevent objects from fall-
ing behind the shield.
Rear wall shields must extend 18" above the top of the
stove or to within 1" of the ceiling, must be centered
behind the stove, and must be a minimum of 48" (1220
mm) wide by 48" high.
Side wall shields must be 48" (1220 mm) wide by 44"
high, and must extend 15" (380 mm) beyond the front
of the stove as measured from a point on the wall that
is on the same plane as the door glass.
Vermont Castings Vigilant
Air Flow
Wall Shield
Stud Wall Fram-
ing
Noncom-
bustible
Spacer and
Fasteners
Drywall
Air Flow
ST248
Fig. 11 Wall shield con-
struction.
ST248
wall shield construction
12/14/99 djt
9