Framing & Finishing; Final Finishing; Gas Specifications; Gas Inlet & Manifold Pressures - Majestic fireplaces NV360 Series Homeowner's Installation And Operating Manual

Decorative gas appliance
Table of Contents

Advertisement

NV360/580 Series
Framing and Finishing
Check appliance to make sure it is levelled
and properly positioned.
1. Choose unit location.
2. Nailing flanges are supplied with the fireplace (found
on the fireplace hearth). To level the box and secure
it firmly in place, remove the nailing flanges from
the hearth and install at the sides of the firebox as
shown in Figure 3.
3. Screw through the slotted holes in the drywall strip
and into pre-drilled holes in fireplace side. Measure
from face of fireplace to the face of the drywall strip
to confirm the final depth.
C
A
B
Fig. 3 Nailing flanges.
Finishing
Noncombustible materials such as brick and tile can
be extended over the face of the unit (Do not cover the
glass door or grille). If a trim kit is to be installed, brick
and tile will have to be installed flush with the side of
this appliance.
Gas Specifications
Model
Fuel
NV360RN
Natural
Millivolt Hi/Lo
NV360RP Propane
Millivolt Hi/Lo
NV580RN
Natural
Millivolt Hi/Lo
NV580RP Propane
Millivolt Hi/Lo
6
Adjustable Drywall Strip
(Nailing Flanges)
Screw
Drywall
Position
Depths
A
1/2" / 13 mm
B
5/8" / 16 mm
C
3/4" / 19 mm
Adjustable
1/2", 5/8" & 3/4"
Spacing
FP1023
FP1023
side nailing flange
1/27/00 djt
Max.
Min.
Gas Control
Input
Input
33,500 23,500
33,500 23,700
45,000 31,500
45,000 31,900
Air Shutter Setting
Model
NV360RN
NV360RP
NV580RN
NV580RP
Gas Inlet & Manifold Pressures
Minimum Inlet Pressure
Maximum Inlet Pressure
Manifold Pressure
NV360 / NV580
Certified to
ANSI Z21.50b-2002 / CSA 2.22b-2002
Vented Gas Fireplace
Units: H31A00, H31B00, I31A00, I31B00

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).

Gas Line Installation

When purging gas line the front glass must
be removed.
The gas pipeline can be brought in through the right
side of the appliance. Knockouts are provided at conve-
nient locations to allow for the gas pipe installation and
testing of any gas connection.
The gas line connection can be made with properly
tinned 3/8" copper tubing, 1/2" rigid pipe or an approved
flex connector. Since some municipalities have addi-
tional local codes, it is always best to consult your local
authority and the CSA-B149.1 installation codes.
For USA installations consult the current National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
Always check for gas leaks with a mild
soap and water solution applied with a
brush no larger than 1" (25 mm). Never
apply soap and water solution with a spray
bottle. Do not use an open flame for leak
testing.
Front
Rear
closed
closed
open
open
closed
closed
open
open
LP
Natural
5.5" w.c.
11" w.c.
14.0" w.c.
14.0" w.c.
3.5" w.c.
11" w.c.
20003565