General Information Assembling Vent Pipes; Flex Vent Pipes - Vermont Castings Brookhaven 20DVT Installation Instructions And Homeowner's Manual

Direct vent model
Table of Contents

Advertisement

Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G =
Combustible
G
6" (152 mm)
Noncombustible
V
2" (51 mm)
Balcony -
with no side wall
M
V
M =
Combustible &
Noncombustible
12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3' (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10' (1 m) of a termination cap must be a minimum of 3' (914 mm) below the termination cap. 3. All
gravity air intakes within 3' (914 mm) of a termination cap must be a minimum of 1' (305 mm) below the termination cap.
Fig. 7a Termination clearances.
Canadian Installations:
Venting system must be installed in accordance with the
current CSA-B149.1 installation code.
USA Installations:
The venting system must conform with local codes and/
or the current National Fuel Gas code ANSI Z223.1/
NFPA 54.
Only venting components manufactured by CFM Corpo-
ration can be used in Direct Vent systems.

Flex Vent Pipes

Before joining the flex vent pipe to the unit, apply a
bead of high temperature sealant* (provided) to the 4"
pipe exiting the fireplace. Secure flex vent piep in place
with a hose clamp (provided).
*Be sure the flex pipe overlaps at least 1" (25 mm) onto
the collars of the fireplace and termination. If the ter-
mination has an internal bead, be sure to overlap and
secure 1" (25 mm) past the bead.
10009459
Outside Corner
V
F
Balcony -
with perpendicular side wall
M
V
Combustible &
Noncombustible
M = 24" (610 mm)
P = 20" (508 mm)

General Information Assembling Vent Pipes

Brookhaven Direct Vent Gas Fireplace
Alcove Applications*
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
No.
of Caps
1
P
2
3
4
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
* Be sure the flex vent is flat and flush with the flue or
outer collar before proceeding. Apply a tug to be sure
the vent will not slip off the collars.
Repeat process with 7" flex vent pipe. The same proce-
dure must be performed on the vent side.
Hose
Clamp
Fig. 8 Apply high temperature sealant to 4" and 7" pipes.
D
C
C
V
E
O
E
= Min. 6" (152 mm) for
non-vinyl sidewalls
Min. 12" (305 mm) for
vinyl sidewalls
O
= 8' (2.4 m) Min.
D
C
Min.
Max.
3' (.9 mm)
2 x D
Actual
6' (1.8 m)
1 x D
Actual
9' (2.7 m)
2/3 x D
12' (3.7 m) 1/2 x D
Actual
Apply High Tem-
perature Sealant
Actual
Actual
584-15
FP1471a
9