Generac Power Systems PWRcell X7600 Series Installation Manual page 26

Hide thumbs Also See for PWRcell X7600 Series:
Table of Contents

Advertisement

Commissioning and Setup
2. See
Figure
6-3. A list of operational modes will be
displayed with the current mode marked with an
asterisk.
NOTE: The list of modes may not include all those
shown in
Figure
6-3.
Figure 6-3. Selecting Operational Modes (2 of 4)
3. See
Figure
6-4. Use the up and down arrows to
highlight the desired mode and press the center
button to select.
Figure 6-4. Selecting Operational Modes (3 of 4)
4. Arrow right and press the center button to select
Confirm.
5. See
Figure
6-5. Verify the mode listed at the top of
the home screen is the desired mode.
Figure 6-5. Selecting Operational Modes (4 of 4)
22
Configuring Custom Grid Settings (optional)
By default, all Generac PWRcell Inverters ship in compli-
ance with UL1741, including IEEE1547. If the system
needs to be configured to comply with a different grid
interconnection standard, activate the new configuration
before proceeding.
Enabling REbus Devices
Electrocution. Never enable any device during an
installation or while wires are exposed. Doing so
could result in death, serious injury, equipment or
property damage.
NOTE: All Generac PWRcell devices are enabled and
009966
configured individually through the Generac PWRcell
Inverter control panel.
Following installation, the inverter must be enabled
before all other REbus devices.
To enable the inverter:
1. See
Figure
the inverter device page.
2. Verify inverter status reads disabled.
009967
Figure 6-6. Enabling Inverter (1 of 4)
3. Press the center button.
4. See
Figure
center button.
009968
Figure 6-7. Enabling Inverter (2 of 4)
Installation Manual for Generac PWRCell Inverter
DANGER
6-6. Use the right arrow key to scroll
6-7. Highlight Enable and press the
(000627)
010010
009656 010011