Interconnected alarms will sound and then stop.
c.
The originating smoke alarm will continue to sound 60 seconds to allow ample time to quickly
find originating alarm.
RESET: To reset the QUICK FIND
on any alarm for at least 10 seconds and then release. Reset after each alarm. The reset
feature will reset all interconnected units.
TROUBLE/SERVICE ALARM: If the smoke alarm chirps 3 times every 40 seconds after the red
LED flashes and cannot be restored to normal operation, the smoke alarm should be replaced.
NEVER use an open flame of any kind to test this smoke alarm. You might accidentally damage
or set fire to the smoke alarm or to your home. The built-in test switch accurately tests the
smoke alarm's operation as required by Underwriters Laboratories Inc. (UL).
(UTHA) Sensitivity Indicating Means
The sensitivity indicating means for this Smoke and Fire Alarm is the use of the analyzer for Smoke
Detectors Model 501-A or 501-A/Bat Aerosol Generator Manufactured by Gemini Scientific Corp.,
1122-B Aster Ave., Sunnyvale, CA 94086.
The Equivalent UL 268 Light obscuration %/Ft as measured by this instrument must be between
1.55% Obs./Ft. and 0.85% Obs./Ft (1.20 + 0.35% Obs./Ft.).
(UTHA) Go/No-Go Field Test
The Go/No-Go test for this smoke and fire alarm is to use one of the following UL listed can-type
aerosol smoke alarm testers. The instructions for use are printed on the canister. Home Safeguard,
Model 25S, No Climb model A3-xxx and SDi model Check02-xxx.
If you choose to use an aerosol smoke product to test the smoke alarm, be certain to use one
that has been Listed to Underwriters Laboratories, Inc. Safety Standards and use it only as
directed. Use of non-UL Listed products or improper use of UL Listed products may affect
the smoke alarm's sensitivity.
NUISANCE ALARM SILENCE FEATURE: This feature is to be used only when a known alarm
condition, such as smoke from cooking, activates the smoke alarm. The smoke alarm Silence
Feature is activated by pushing and releasing the Silence button on the smoke alarm cover. The
smoke alarm will automatically reduce sensitivity and the red LED will blink on approx. every 2
seconds to indicate the alarm is in the Silence mode. The smoke alarm will gradually regain normal
sensitivity and sound the alarm if particles of combustion are still present. The 8-12 minute Silence
feature may be used repeatedly until the air has cleared, by pushing and releasing the Silence
button again. Resetting the smoke alarm after a nuisance alarm is recommended.
NOTE: If the Test button is pressed and held during the Silence mode, the smoke alarm will be
tested normally. Upon the release of the Test button, the Silence mode will be restarted.
Before using the alarm Silence Feature, identify the source of smoke and be certain that safe
conditions exist.
(UTHA) MAINTENANCE:
The smoke alarm is virtually maintenance free. However, under dusty conditions, a vacuum hose
may be used to clear the sensing chamber of dust.
Clean the smoke alarm at least once a month to remove dust, dirt, insects or debris. Always turn
off power to smoke alarm before cleaning. Using a soft brush or wand attachment to a vacuum
cleaner, vacuum all sides and cover of smoke alarm. Be sure all the vents are free of debris.
Disconnect AC power before changing battery. Shock hazard exists if AC power is miswired.
The smoke alarm uses a 9 Volt battery. The battery should last for at least one year under normal
operating conditions. The smoke alarm has a low battery indicator, an audible beep or chirp. It will
operate at approx. 40 second intervals for a minimum of 7 days. When this indication occurs, replace
the battery with an Alkaline type (Energizer #522, Duracell #MN1604), Carbon-Zinc type (Gold Peak
#1604S) or Lithium type (Ultralife U9VL-J or Ultralife U9VL-J-P) from your local retailer.
LITHIUM Battery Models only - The LITHUM battery is warranted to last for 10 years under normal
operating conditions. Replace the battery with only LITHIUM type: (ULTRALIFE: U9VL-J or Ultralife
U9VL-J-P).
®
Alarm Origination condition, press and hold the Test button

BACKUP BATTERY REPLACEMENT