Section 4: Applications; Nac Outputs; Power Outputs - Honeywell Notifier ACPS-610/E Manual

Addressable charger/power supply
Table of Contents

Advertisement

4.1 NAC Outputs

NOTE: Active NACs will disable the power supply's charger.

4.2 Power Outputs

Power
Output
Circuit 2
Power
-OUT1
Output
Circuit 1
+OUT1
TB3
CAUTION: Risk of equipment damage!
!
When the battery charger is disabled, the total power output continuous current is 2.5 Amps.
ACPS-610/E Manual — P/N 53018:A1 07/31/2007

Section 4: Applications

*
*
TB3
TB4
Note: The NAC outputs shown above are in a non-coded configuration.
Figure 4.1 Four NAC Outputs
-OUT2
+OUT2
Figure 4.2 General Purpose Power Output
*
TB5
TB4
TB5
Note: The output is power-limited and non-
supervised. Use an end-of-line relay to supervise.
*
Use listed end-of-line
resistor, P/N
ELR-2.2K, (included)
to terminate Style Y
(Class B) NAC. ELRs
*
are not be used when
Style Z (Class A)
return is wired.
TB6
+OUT3
Power
Output
Circuit 3
-OUT3
Power
+OUT4
Output
Circuit 4
-OUT4
TB6
39

Hide quick links:

Advertisement

Table of Contents
loading