User Control Levels; Level Definition; User Passwords - Honeywell MORLEY IAS DX Series User Manual

Table of Contents

Advertisement

Dimension Series

2 User Control Levels

2.1 Level Definition

The DX1e, DX2e and DX4e Fire Alarm Control Panels have three user control levels.
At all three levels, the LED Displays indicate the condition of the installation, the Zone LED Displays
indicate the location of any fire alarm and the alphanumeric display gives more detailed fire alarm,
fault, and test or disablement information.
At USER LEVEL 1, all the displays are functional but the front panel control keys are inhibited.
At USER LEVEL 2, all front panel controls are functional and some system operation parameters and
functions can be changed. User Level 2 is reached by entering a password from level 1.
At USER LEVEL 3, all front panel controls are functional and full system configuration and
programming is possible. User Level 3 is reached by entering a password from either Level 1 or Level
2. User Level 3 is intended for use by the system installer / maintenance contractor.
EN54-2 5.1
EN54
Viewing
Suppressed
Information.

2.2 User Passwords

Up to ten USER LEVEL 2 passwords can be programmed into the panel.
The USER LEVEL 2 passwords can be assigned / changed at Level 3 by the installer / maintenance
contractor. Level 2 passwords do not allow access to Level 3 functions.
User Manual
All of the mandatory indications that may not be suppressed during a
fire alarm condition are shown using Light Emitting (LED) Indicators.
Fire Alarms are shown using LED Indicators for each zone.
It is possible to view all other conditions such as points in fire, faults,
zones in test and disablement conditions using the navigation (arrow)
keys at Level 1.
Document No.996-148-000-5, Revision: 5
MORLEY-IAS
Page 5