Swann Smith's Caspian EC Series Installation And User Manual

Fan convectors
Hide thumbs Also See for Smith's Caspian EC Series:

Advertisement

Quick Links

Caspian - EC variants
Installation and user manual
60 | 90 | 120 | 150 | 180
EC Series Fan Convectors
Issue 001 | July 2020
ENGLISH | UK | IRL | SmithsEP.co.uk
Issue 001 - July 2020 | SmithsEP.co.uk | 1

Advertisement

Table of Contents
loading

Summary of Contents for Swann Smith's Caspian EC Series

  • Page 1 Caspian - EC variants Installation and user manual 60 | 90 | 120 | 150 | 180 EC Series Fan Convectors Issue 001 | July 2020 ENGLISH | UK | IRL | SmithsEP.co.uk Issue 001 - July 2020 | SmithsEP.co.uk | 1...
  • Page 2: Table Of Contents

    Contents Introduction Introduction Suitable for Caspian (UV, FF, EXT, SL, TT) Declaration of conformity These heaters must not be installed in wet rooms Symbols used in this guide or other high humidity areas. Important safety and installation instructions These heaters are designed for use on standard Product Information two-pipe pumped central heating systems with a maximum water temperature of 86°C and a...
  • Page 3: Declaration Of Conformity

    Declaration of conformity Symbols EC Declaration of conformity This manual contains information and prescriptions marked by the following symbols. We, Smith’s Environmental Products Limited 1-2 Blackall Industrial Estate South Woodham Ferrers Ignoring these safety provisions Chelmsford marked by the symbol “caution: Essex CM3 5UW hazard”...
  • Page 4: Important Safety And Installation Instructions

    Important safety and installation instructions Prior to installation, read these installation and operating instructions. The installation and operation should also be in accordance with national regulations and accepted codes of good practice. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  • Page 5 7. Electric connection IMPORTANT: Connection to the power supply must be effected by means of a fixed power cable which is fitted with a plug-type connection or a two pole isolating switch with a minimum contact opening of 3 mm. Electrical connection must be carried out by a qualified electrician and in accordance with local regulations and both data on the name-plate and the appropriate diagram inside the terminal box cover.
  • Page 6: Product Information

    Product dimensions Caspian UV Caspian SL Electrical supply in this side Electrical supply in this side Pipe centres Model Pipe centres Model 1195 1195 1495 1495 1795 1795 Caspian FF Caspian TT Electrical supply in this side Electrical supply in this side Pipe centres Pipe centres Model...
  • Page 7: Product Performance

    Product performance Heat output - EC Model Control 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C Reference Speed Voltage VDC 0.85 1.20 1.45 1.80 2.16 2.35 2.73 3.08 3.40 1.02 1.53 1.92 2.37 2.76 3.18 3.58 4.05 4.38 EC 60 High 1.18 1.85...
  • Page 8 Product performance Model Hydraulic Water Nominal Weight (KG) Reference Speed Resistance (KPA) Capacity (L) 1.38 1.69 EC 60 23.00 0.92 High 2.00 4.70 5.85 EC 90 36.00 1.50 High 7.00 17.78 20.59 EC 120 45.00 2.08 High 23.40 22.23 29.46 EC 150 60.00 2.58...
  • Page 9: Mounting Options

    Mounting options ➠ ➠ Ceiling (edge) Ceiling (centre) Wall Wall ➠ ➠ Floor Floor Caspian SL Caspian UV ➠ Ceiling (edge) Ceiling (centre) ➠ ➠ ➠ Wall ➠ Wall ➠ ➠ Floor Floor Caspian TT Caspian FF The controls used varies upon the positioning in the room.
  • Page 10: Wiring Diagrams

    Wiring diagrams Caspian CL 60 L.T.C +10V Control Ground Speed Control Tacho Thermostat Link (optional) Mains Supply Caspian CL 90/120 EC DC Filter Note: The earth link is directly above the L.T.C negative terminal on +10V the EC DC filter Control Ground Speed Control...
  • Page 11: Installation

    Installation Note: We recommend the use of full-flow service valves. The valves should be accessible after completion of the installation. We also advise the 1. Unlock the front access panel fitting of an air vent at the highest point on either the flow or return pipe to remove any air trapped Unlock and lower the front access panel using the within the system.
  • Page 12 Accessory installation The fused spur must not be directly below the heater and must be accessible after the installation is complete. All electrical work should be carried A wide range of accessories are available, most out in accordance with current IEEE regulations. of which are factory fitted.
  • Page 13: Commissioning

    Commissioning Heating operation 1. Turn on the electrical supply at the fused spur. Ensure the central heating system is ON. Switch on the power supply to the unit. Set 2. Turn the thermostat control (if fitted) to the thermostat control (if fitted) to the desired maximum.
  • Page 14: Fault Finding

    Fault finding Providing the power supply is switched on the room thermostat (if fitted) is calling for heat the heater will switch on and off automatically with the central heating system. In the event of any difficulty, please contact us on +44 (0) 1245 324560. It will be helpful if you do not disconnect the heater from the central heating system.
  • Page 15: Registering Your Product

    Registering your product Disposal As part of the policy of continuous product Thank you for purchasing a Smith’s product. It has improvement, Smith’s Environmental Products LTD been designed and manufactured to the highest reserves the right to alter specification without quality standards to ensure it gives you efficient prior notice.
  • Page 16 Happy to help To view the full product information download the datasheet at: Smith’s Environmental Products Ltd is one of the leading manufacturers of heating and cooling www.SmithsEP.co.uk products in the UK. We are committed to achieving the highest standards and our faith is For product information, customer services or supported by a free parts and labour guarantee sales support call us on +44 (0) 1245 324900...