Swann Smith's Caspian CTFF Series Installation, Commissioning And User Manual
Swann Smith's Caspian CTFF Series Installation, Commissioning And User Manual

Swann Smith's Caspian CTFF Series Installation, Commissioning And User Manual

Advertisement

Quick Links

Caspian
CTFF
®
EC variants with Smart Controls
Installation, commissioning
and user manual
CT60FF | CT120FF
EC Series Fan Convectors
Issue 001 | October 2023
ENGLISH | UK | IRL | SmithsEP.co.uk
Issue 001 - October 2023 | SmithsEP.co.uk | 1

Advertisement

Table of Contents
loading

Summary of Contents for Swann Smith's Caspian CTFF Series

  • Page 1 Caspian CTFF ® EC variants with Smart Controls Installation, commissioning and user manual CT60FF | CT120FF EC Series Fan Convectors Issue 001 | October 2023 ENGLISH | UK | IRL | SmithsEP.co.uk Issue 001 - October 2023 | SmithsEP.co.uk | 1...
  • Page 2: Table Of Contents

    Contents Introduction Introduction These heaters must not be installed in wet rooms or other high humidity areas. Declaration of conformity Symbols used in this guide These heaters are designed for use on standard two-pipe pumped central heating systems with Important safety and installation instructions a maximum water temperature of 86°C and a maximum pressure of 6 bar (88lbs/in.).
  • Page 3: Declaration Of Conformity

    Declaration of conformity Symbols EC Declaration of conformity This manual contains information and prescriptions marked by the following symbols. We, Smith’s Environmental Products Limited 1-2 Blackall Industrial Estate South Woodham Ferrers Ignoring these safety provisions Chelmsford marked by the symbol “caution: Essex CM3 5UW hazard”...
  • Page 4: Important Safety And Installation Instructions

    Important safety and installation instructions Prior to installation, read these installation and operating instructions. The installation and operation should also be in accordance with national regulations and accepted codes of good practice. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
  • Page 5 8. Electrical connection Important: Connection to the power supply must be effected by means of a fixed power cable via a two pole isolating switch (fused spur) with a minimum contact opening of 3mm. The fused spur must not be directly below the heater but should be accessible after completion of the installation.
  • Page 6: Product Dimensions

    Product dimensions Caspian CTFF 270 242 Electrical supply Pipe Centres Pipe Entry in this side Model 1195 Installation Cutaway – T-Bar Ceiling Hanging Hanging Bolt Bolt Heater Unit T-Bar T-Bar Tile Tile Grille / Casing 6 | SmithsEP.co.uk | Issue 001 - October 2023...
  • Page 7: Product Performance

    Product performance Heat output - EC Model Control 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C Reference Speed Voltage VDC 0.85 1.20 1.45 1.80 2.16 2.35 2.73 3.08 3.40 1.02 1.53 1.92 2.37 2.76 3.18 3.58 4.05 4.38 EC 60 High 1.18 1.85...
  • Page 8: Control Mounting Options

    Control mounting options/configurations Internally mounted - To be specified at time of Wall mounted - Standard product order (built to order) (remote) (tamper proof) Wiring diagram - Master Slave Master Slave Slave connection Mains connection Slave Mains connection connection Internal control option (control adjacent to wiring Remote / flush control options (electrical panel) connection moved adjacent to wiring panel)
  • Page 9: Wiring Diagrams

    Wiring diagram - Standard Valve Acutator 230 / 10V INTERFACE SUPPLY SLAVE 24 VAC OUTPUT OUTPUT Where factory modification made separate diagram to be supplied Issue 001 - October 2023 | SmithsEP.co.uk | 9...
  • Page 10: Installation

    Installation 1. Unlock the front access panel Unlock and lower the front access panel using the keys supplied. The keys come cable tied to the back of the heater. Note: The system must be flushed prior to fitting this heater. Failure to comply with this may effect the warranty.
  • Page 11: Installation - Remote Smart Controller

    5. Electrical supply and electrical 5. Fasten body of thermostat and the mounting plate. See Fig 5. connection 6. When using external pattress box assemble as shown. See Fig 6. Electrical supply to the unit must be nominal 230VAC 50~Hz. Electrical connection to the product is via a 3 way terminal block inside the product (L, N, E), on electrical panel.
  • Page 12: Commissioning

    Commissioning Connecting remote smart controller to the heater 1. Turn on the electrical supply at the fused spur. 1. Feed the connector end of the wire harness 2. Set the thermostat to maximum using the increase button on the controller. through the cut outs in the back or underside of the unit.
  • Page 13: User Guide For Wi-Fi Thermostat

    Quick user guide for Wi-Fi Button functions Thermostat Function Increase Button Decrease Button Fan Speed Low, Medium, High, Auto, Off Long press Short press (2sec) Heat/Cool/Eco Digital Offset, Time Mode selection Button Permanent override Programmable Program- AUTO schedule mable Heat/Cool/Eco Offset selection Time&Date...
  • Page 14: Getting Started - Programming

    LCD Icon descriptions Getting started All units are factory configured in off-line stand alone mode and tested for function when built. Should your unit require setup from storage or reconfiguration to “Smart Home” App control follow the steps below to ensure successful setup and operation.
  • Page 15 1. When powered for the first time the control 5. Select the thermostat mode, although this unit is heating only by setting heating and cooling will boot (Software version will appear) after a allows the use of fan only/ventilation sort time the display will change to show if required.
  • Page 16 Changing from offline Scan for equipment Press from the App and mode to online mode follow the on screen instructions. If you want to use the internet App and the Universal Gateway Hub UG600 (available as an accessory product code: HACA33130), you need to change your thermostat settings from offline mode to online mode.
  • Page 17 Factory reset User Guide If you have made an error or need to change For further information and to view detail of set your system parameters, or want to return to up, operation and parameters, please consult the the factory settings, please follow steps below. full manual at: By performing this action you will lose all your https://salus-controls.com/uk/product/fc600/#downloads...
  • Page 18: Maintenance

    Maintenance Warning! Isolate from the electrical supply The fan(s) and motors should not require servicing. before performing any work on the unit. Please contact your supplier if damaged. The internal air filter is removable for servicing. To replace filter use reverse the removal To gain access to the filter unlock and lower the instructions and ensure the lower front access front access panel, remove the 2 screws from the...
  • Page 19: Accessories

    Accessories Disposal As part of the policy of continuous product Air inlet filters for all models improvement, Smith’s Environmental Products LTD Universal Gateway Hub UG600 for use with reserves the right to alter specification without internet App control prior notice. For accessories or spares please refer to our price Products with this symbol (crossed out wheelie list, contact your supplier or Smith’s Environmental...
  • Page 20 Happy to help To view the full product information download the datasheet at: Smith’s Environmental Products Ltd is one of the leading manufacturers of heating and cooling www.SmithsEP.co.uk products in the UK. We are committed to achieving the highest standards and our faith is For product information, customer services or supported by a free parts and labour guarantee sales support call us on +44 (0) 1245 324900...

This manual is also suitable for:

Smith's caspian ct60ffSmith's caspian ct120ff

Table of Contents