GUD50T/A1-K +GU50W/A1-K
① .
Power cord 3×1.5mm
② .
Power cord 3×1.0mm
③ .
Communication cords 2×0.75mm
④ .
Communication cords 2×0.75mm
GU71T/A1-K +GU71W/A1-K
GU85T/A1-K +GU85W/A1-K
① .
Power cord 3×2.5mm
Power cord 3×1.0mm
② .
Communication cords 2×0.75mm
③ .
Communication cords 2×0.75mm
④ .
GU100W/A1-M, GU125W/A1-M ,GU140W/A1-M, GU160W/A1-M:
GU100T/A1-K +GU100W/A1-M
GU125T/A1-K +GU125W/A1-M
GU140T/A1-K +GU140W/A1-M
GU160T/A1-K +GU160W/A1-M
Power cord 5×1.5mm
① .
② .
Power cord 3×1.0mm
Communication cords 2×0.75mm
③ .
④ .
Communication cords 2×0.75mm
(5) Electrical wiring of indoor unit
① .
High and low voltage wires should be led through different rubber rings of the
electric box cover.
② .
Do not bundle up the connection wire and communication wire of wired control
or lay them side by side, otherwise errors will occur.