MESSAGE
UPS LDEV <nnn> reports UPS "Overload Shutdown" condition.
(UPSERR 0196)
CAUSE
The specified PowerTrust unit reported an "Overload Shutdown" condition.
Too much power was being drawn from the PowerTrust unit AC output by the
computer equipment being powered from this PowerTrust unit. An improper
system installation has put too much load on the PowerTrust unit, or the
computer equipment being powered may be malfunctioning.
ACTION
1. Reduce the load on the PowerTrust unit by powering off some
2. Check for an improper system hardware installation. Correct the
3. If the system installation is not the problem, find and replace the
MESSAGE
UPS LDEV <nnn> reports UPS "High Ambient Temperature
Shutdown" condition. (UPSERR 0197)
CAUSE
The specified PowerTrust unit reported a "High Ambient Temperature
Shutdown" condition. The temperature of the PowerTrust unit hardware
became too high to permit safe operation, and the PowerTrust unit turned
itself off to prevent equipment damage. The computer room temperature is too
high, or there may be a hardware malfunction in the PowerTrust unit.
ACTION
If the computer room has become too warm, take steps to cool the room. If
room temperature is not the problem, then replace the faulty PowerTrust unit.
Appendix B
non-critical system component.
system installation to reduce the loading on the PowerTrust unit.
faulty system hardware component that is overloading the
PowerTrust unit.
MPE/iX UPS Monitor Error Messages
Alarm Status Messages
B-7