Field Replaceable Units
Removal and Replacement Procedures
NOTE
The UPS requires single-phase input power (in contrast to 3-phase).
Single-phase power may be obtained in one of the following ways:
a. Line-to-neutral: 200-240V across a phase wire (hot wire) and a
b. Line-to-line: 200-240V across two different phase wires (hot wires).
In some countries, the UPS must be supplied line-to-line in order to obtain
200-240V. Other countries require line-to-neutral to obtain 200-240V. In no
case should the input voltage exceed the rating of 200-240V.
Output wiring for worldwide (hardwired) version:
Line (or Line 1): Connect wire to the L1 terminal
Neutral (or Line 2): Connect wire to the L2/N terminal
Earth Ground: Connect the GREEN or GREEN/YELLOW wire to the terminal
marked with the following symbol:
Tighten the terminal block screws to the following torque specifications:
For Line and Ground Terminals: 1.2 - 1.4 Nm (10.6 - 12.3 lb-in)
5. If all repairs to the UPS have been completed, or if the UPS is being converted on
site, it can be powered on and returned to service. Follow these steps:
a. Make certain that the Bypass switch is in the
b. Connect the AC line cord to the AC source.
c. Turn ON the MAIN INPUT circuit breaker.
d. Turn the UPS/BATTERY switch to
Wait for the green Enable LED to come on.
e. Check that the Caution LED is off.
If it is on, refer to "Caution LED" in Chapter 6.
f. Turn the Output On/Output Off switch to
D-16
neutral wire.
position.
NORMAL
.
ENABLE
.
Output On
Appendix D