Determine percent of voltage imbalance:
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
Unit operation on improper line voltage or excessive phase imbal-
ance may be considered abuse and any resulting damage may not
be covered by Carrier warranty.
All wiring must be in accordance with local or NEC (National
Electrical Code) regulations.
POWER WIRING
The units must have adequate overcurrent protection, fuses, or
HACR (Heating, Air-Conditioning and Refrigeration) breakers,
according to the national and applicable local codes.
UNIT
V-PH-Hz
50XCW
208/230-3-60
06
460-3-60
575-3-60
208/230-3-60
08
460-3-60
575-3-60
208/230-3-60
12
460-3-60
575-3-60
208/230-3-60
14
460-3-60
575-3-60
208/230-3-60
16
460-3-60
575-3-60
208/230-3-60
24
460-3-60
575-3-60
LEGEND
LRA
— Locked Rotor Amps
NEC
— National Electrical Code
RLA
— Rated Load Amps
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR circuit breaker.
Canadian units may be fuse or circuit breaker.
2. Wire sizing amps are a sum of 125% of the compressor RLA plus
100% of indoor fan motor FLA (full load amps).
3. Motors are protected against primary single phasing condition.
4. Indoor-fan motors are 3-phase motors of same voltage as unit.
7
457
Table 2 — Electrical Data
VOLTAGE
RANGE
Min
187
414
518
187
414
518
187
414
518
187
414
518
187
414
518
187
414
518
For field power connections, all main power wiring enters the unit
through a factory-punched access hole under the control box. At-
tach power wires to the power connections on the main power ter-
minal block in the unit control box. Be sure to install a ground
wire.
CONTROL WIRING
All units require an accessory thermostat package to complete the
unit control system. For a room-mounted thermostat, the thermo-
stat may be mounted in an appropriate location in the conditioned
space. Route the wires from the thermostat to the low voltage con-
nection of the control box. Connect wires to the low voltage termi-
nal block. See Fig. 18. The fan switch on the thermostat will con-
trol fan operations.
FREEZE PROTECTION THERMOSTAT
A standard freeze protection thermostat is factory-installed.
COMPRESSOR
NO. 1
Max
RLA
253
18.3
506
8.8
632
6.6
253
23.0
506
11.0
632
8.0
253
15.6
506
7.8
632
5.8
253
19.6
506
8.2
632
6.6
253
28.7
506
13.3
632
10.0
253
40.7
506
19.3
632
15.6
19
COMPRESSOR
NO. 2
LRA
RLA
136
66
55
149
75
54
110
15.9
52
7.1
39
5.1
136
19.2
66
8.7
55
6.9
191
23.0
100
11.0
78
8.0
240
28.7
140
13.3
107
10.0
LRA
110
52
39
136
66
55
149
75
54
191
100
78

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents