XNX Universal Transmitter

mA Levels

This option allows the user to select mA output levels for inhibit,
fault, and overrange. Beam block and low signal apply to
Searchline (see the table in the next column).
Figure 100. mA Levels menu
Using the
switches, move to the mA output to be changed
and use
to select it.
Figure 101. Set mA Levels for Warning screens
Use the
switches to decrease or increase the value until the
desired value appears. Use
next setting. Repeat for each setting to be changed.
The default values and available output ranges for Inhibit,
Warning, Overrange, Beam Blocked, and Low Signal are shown in
the following table. See
Warnings and Faults
Installation and Operation
to select the value and move to the
for more information.
Figure 102. Set mA Levels for Inhibit screen
After all changes have been made, use the
move to the 'ü' and use
save the settings. If 'ü' is not selected, none of the changes will
be saved.
Figure 103. mA Settings Saved screen

Calibration Interval

Calibration Interval allows a desired interval for sensor
calibration to be set for sensors attached to the transmitter. The
transmitter will generate a warning when the interval is reached.
Figure 104. Calibration Interval menu
Calibration Interval will not appear when an IR personality board
is attached and the mA sensor type is set as 'Other mA Sensor'.
79
Output (mA)
Signal
Default
I
Inhibit
2.0
W Warning
3.0
O
Overrange
21.0
B
Beam Blocked
1.0
L
Low Signal
1.0
switches to
on the front panel to accept and
Min
Max
1.0
3.5
1.0
3.5
20
22
1.0
4.0
1.0
4.0