Battery Replacement

Under normal conditions, the original batteries in your UPS will last many years. See Safety section
before replacing batteries. The batteries are designed for hot-swap replacement (i.e. leaving the UPS in
ON mode), but qualified service personnel may wish to put the UPS in the OFF mode before proceeding.
1U UPS Models

Specifications

Model
Series #
Input
Nominal Voltage/Frequency:
Suggested Circuit:
Output
Capacity (VA/Watts)
On Line Nominal Voltage/Waveform:
On Battery Nominal Voltage/Waveform:
Battery Recharge Time (to 90% charge)
Typical Transfer Time
Approvals:
ALL MODELS: Voltage-Regulated Output Voltage Range (230V +/- 9%); On Battery Output Voltage Range (230V +/- 5%); AC Surge Suppression (exceeds IEEE 587
Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Protection Modes (H to N).
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage
V
: DC Voltage
Procedure
Remove Front
1
Panel
Disconnect
2
Batteries
1
6
3
Remove/Dispose of
Batteries
4
Add Batteries
Connect Batteries
5
Attach connectors: black-
to-black and red-to-red.
2
5
6
Replace Front Panel
3
4
SMX500RT1U
SMX750RT1U
AGSMX500RT1U
AGSM751SRM1U
230VAC, 50/60Hz
230VAC, 50/60Hz
10 amp
500/300
230VAC/sine wave
230VAC/sine wave
230VAC/PWM sine wave
230VAC/sine wave
2-4 hrs.
2-4 ms.
CE, GOST, SASO, IRAM
CE, GOST, SASO, IRAM
SMX1000RT2U
AGSM4724
230VAC, 50/60Hz
10 amp
10 amp
750/450
1000/700
230VAC/sine wave
230VAC/sine wave
2-4 hrs.
2-4 hrs.
2-4 ms.
2-4 ms.
CE, GOST, SASO, IRAM
12
2U UPS Models
1
2
3
SMX1500XLRT2U
SMX3000XLRT2U
AGSM152DRTI2U
AGSM4878
230VAC, 50/60Hz
230VAC, 50/60Hz
10 amp
1500/1000
3000/2250
230VAC/sine wave
230VAC/sine wave
230VAC/sine wave
230VAC/sine wave
2-4 hrs.
2-4 ms.
CE, GOST, SASO, IRAM
CE, GOST, SASO, IRAM
6
5
4
20 amp
2-4 hrs.
2-4 ms.

Advertisement