Napoleon Vector Series Installation Manual page 28

Natural/propane gas, the appliance is suitable for the optional dynamic heat control system
Hide thumbs Also See for Vector Series:
Table of Contents

Advertisement

Available languages

Available languages

rough framing - before appliance installation
EN
see-thru
1" [25mm] minimum
all sides for sections
of vertical venting.
When passing
through a
ceiling, use
fi restop spacer
W500-0028 (not
supplied)
L
Horizontal vent sections: A minimum clearance of 3" (76mm) on the top outside of the enclosure and 2" (51mm) on
the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to combustibles is required.
Horizontal vent sections within enclosures require a minimum clearance of 6" (152mm) at the top of the vent pipe.
Vertical vent sections: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is re-
quired except for clearances in appliances enclosures. Vertical vent sections within enclosures require a minimum clear-
ance of 1" (25mm) around the vent pipe.
minimum clearance
Ref
LV38-1
L
note:
The LV series requires a minimum enclosure/ceiling height, as illustrated (dimension L), measured from the bottom of
the appliance. For temperature requirements, this area must be left unobstructed. Some venting confi gurations that
require more vertical rise will require a larger enclosure to provide minimum vertical clearance between vent pipes and
combustibles.
28
W415-2034 / A / 10.18.19
SAFETY BARRIER
LV50-2
73" (185.4cm)
note:
Shaded components (fi nish framing) must be
non-combustible materials.
3" [76mm] (minimum all sides
for sections of horizontal vent-
ing) outside of enclosure.
14"
(35.6cm)
min.
LV62
LV74
91" (231.1cm)
6" [152mm]
minimum
(inside enclosure)
3" [76mm] top (out-
side of enclosure)
2" [51mm] sides /
bottom (outside of
enclosure)
0" to non-
combustible fi nishing
such as brick and
stone
When passing
through a wall, use
fi restop spacer
W615-0162 (sup-
plied with W010-
4178 fi restop spacer
assembly)
0" to side standoffs
1/2" fi nishing fl ange
(4 sides)
0" to base of the
appliance