Binary Outputs; Analog Outputs; To Wire Inputs And Outputs - Carrier RTU Open v5 Installation And Startup Manual

Hide thumbs Also See for RTU Open v5:
Table of Contents

Advertisement

Installing the RTU Open

Binary outputs

The RTU Open has 8 binary outputs. You can connect each output to a maximum of 24 Vac/Vdc. Each output is a
dry contact rated at 3 A, 24 V maximum, and is normally open.
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate

Analog outputs

The RTU Open has 2 analog outputs that support voltage or current devices.
AO-1 - 2-10 Vdc or 4-20 mA (Configure on jumper J3)
AO-2 - 0-10 Vdc or 2-10 Vdc
NOTE The controlled device must share the same ground as the controller. When used as a 4-20 mA output, the
load must have an input impedance of 500 Ohms or less. If the output is used as a voltage type output, then the
load impedance must be 10K ohms or greater.

To wire inputs and outputs

1
Turn off the RTU Open's power.
2
Connect the input wiring to the screw terminals on the RTU Open.
3
Turn on the RTU Open's power.
4
Set the appropriate jumpers on the RTU Open.
J3
W1
W2
W3
W4
W5
RTU Open v5
Installation and Start-up Guide
AO - 1
Battery Jumper
Format Jumper*
Input 11 mA Jumper
Input 11 Thermistor
Input 10 mA Jumper
0 - 10 Vdc/4-20 mA
In (Do not remove)
Out
Out (mA not used on this channel)
In (default position)
Out (mA not used on this channel)
16
CARRIER CORPORATION ©2018
All rights reserved

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents