Installing the UC Open

Input wiring specifications

Input
0–5 Vdc
Thermistor
Dry contact
Pulse counter TLO
ZS sensors
Wireless Adapter for
wireless sensors
Equipment Touch
TruVu™ ET Display

Inputs

The UC Open has inputs that accept the following signal types.
These
inputs...
All
All
IN-1, IN-2
All

Binary outputs

The UC Open has 5 binary outputs. You can connect each output to a maximum of 24 Vac/26 Vdc. Each output is
a dry contact rated at 1 A, 24 V maximum and is normally open.
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate
UC Open
Installation and Start-up Guide
Maximum length
500 feet
(152 meters)
500 feet
(152 meters)
See Wiring devices to the UC Open's Rnet port (page 11).
Support this signal
type...
Description
Precon type 2 (10 kOhm at 77°F/25°C)
Thermistor
Input voltage for IN-5: 1 to 2.52 Vdc
Input voltage for all other inputs: 0.33 to 2.52 Vdc
Dry contact
A 3.3 Vdc wetting voltage detects contact position, resulting in a 0.3 mA
maximum sense current when the contacts are closed.
0–5 Vdc
The input impedance of the UC Open is approximately 30 kOhm.
Pulse counter
Pulse counting up to 4 pulses per second.
Minimum pulse width (on or off time) required for each pulse is 100
msec.
Minimum gauge
Shielding
22 AWG
100 feet
(30.4 meters) unshielded
100 - 500 feet shielded
22 AWG
100 feet
(30.4 meters) unshielded
100 - 500 feet shielded
8
CARRIER CORPORATION ©2019