Balance Point; Cooling Cycle; Balance Point Chart - Carrier 50ZH Series Installation, Start-Up And Service Instructions Manual

3-phase packaged heat pump
Hide thumbs Also See for 50ZH Series:
Table of Contents

Advertisement

80000
OUTDOOR COIL
Check Valves
A
Ck)sed
B
Open
C
Ck)sed
D
Open
LEGEND
LCS
Loss of Charge
Switch
]
Acutrol
Metering
Device
r_
Check Valve (Arrow
indicates
direction
of flow)
LCS
INDOOR COIL
=
COOLING
CYCLE
1. Hot gas from compressor
flows through
the 4-way valve
and is
directed
to the heating
liquid
line check valve.
It is then con-
densed and subcooled through converging circuits. Refrigerant leaves
the outdoor coil by way of the strainer
and the check valve in the
cooling liquid line.
2. The
refrigerant
then
feeds
the indoor
coil thR)ugh
the Acutrol
metering
device on each circuit.
3. Each circuit evaporates
the refrigerant
and the circuits
are com-
bined in the indoor coil header with some of the circuits
flowing
through
the check valve.
4. The refrigerant
then flows through the 4-way valve, accumulator,
and back to the compressor.
Fig. 26-Typical
Heat Pump Operation,
Cooling
Mode
Balance Point Worksheet
C95044
k-
o_
eL)
S_
c
D
70000
60000
50000
40000
30000
20000
10000
-10
10
20
30
40
Outdoor Air Temp (Deg F)
Fig. 27-50ZH Balance
Point Chart
21
5O
6O
C01038rev2