Dry Coil Air Delivery Horizontal Discharge; Wet Coil Pressure Drop; Filter Pressure Drop - Carrier 50ZH Series Installation, Start-Up And Service Instructions Manual

3-phase packaged heat pump
Hide thumbs Also See for 50ZH Series:
Table of Contents

Advertisement

Table 4--Dry
Coil Air Delivery* Horizontal Discharge
(Deduct 10 percent for 208 Volt Operation)
Unit
030
036
042 t
048 t
080 t
Motor Speed
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
230 AND 460 VOLT
External Static
Pressure
(in. wg)
Watts/CFM
0,1
0.2
0.3
0,4
0.5
0.8
0.7
0.8
Watts
288
285
282
279
274
268
261
Cfm
875
820
802
734
668
582
478
Watts
390
383
378
369
360
350
340
Cfm
1131
1090
1038
978
917
830
721
Watts
528
520
510
495
480
460
450
Cfm
1891
1338
1285
1200
1115
1018
920
Watts
450
435
420
400
380
335
326
311
Cfm
1231
1218
1204
1120
1008
950
863
751
Watts
470
450
445
410
388
359
338
321
Cfm
1302
1264
1205
1163
1081
940
873
783
Watts
660
635
610
575
540
505
485
460
Cfm
1700
1660
1581
1450
1297
1190
1095
999
Watts
478
458
440
411
378
350
327
317
Cfm
1303
1270
1224
1179
1126
1022
911
816
Watts
481
468
450
438
404
370
338
320
Cfm
1310
1280
1241
1181
1110
1022
943
811
Watts
798
678
647
618
578
540
500
Cfm
1736
1688
1618
1510
1421
1309
1187
Watts
801
760
730
688
650
600
Cfm
1898
1841
1757
1682
1564
1429
Watts
Cfm
Watts
870
842
818
782
696
632
Cfm
2000
1903
1799
1718
1625
1446
Watts
890
850
810
790
735
680
580
480
Cfm
1834
1820
1791
1762
1703
1640
1415
1159
Watts
1040
1018
1000
950
890
835
790
650
Cfm
2230
2102
2025
1960
1901
1855
1752
1468
Watts
1073
1038
1001
958
898
840
800
691
Cfm
2230
2202
2160
2122
2052
1926
1791
1588
0.9
460
1060
570
1333
828
1385
422
950
58O
1121
575
1202
t 480-v motors are 2-speed.
Air delivery values are based on operating
voltage of 230-v. or 460-v., dry coil, without filter or electric heater. Deduct wet coil filter, and electric heater pressure drops
to obtain external
static pressure availabe
for ducting.
Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity.
Evaporator
coil frosting may occur at airflows below
this point.
Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.
Table 5--Wet
Coil Pressure Drop
Table 6--Filter
Pressure Drop (In. wg)
UNIT SIZE
UNiT
FILTER
CFM
5OZH
SiZE
SIZE
50ZH
(IN.)
500
600 700
800 900 1000 1100 1200
030
080-042 24x24
0.06 0.07 0.08 0.08 0.09 0.09
0.09
0.10
048, 060 24 x 30
038
042
048
060
AIRFLOW
(CFM)
900
1000
1200
1000
1200
1400
1600
1000
1200
1400
1600
1400
1600
1800
1700
1800
2100
2300
PRESSURE
DROP
(IN. WG)
0.08
0.08
0.08
0.07
0.09
0.11
0.12
0.04
0.08
0.08
0.09
0.07
0.08
0.09
0.07
0.08
0.09
0.10
18
1300
1400
0.11
0.12
0.08
0.09
UNiT
FILTER
CFM
SIZE
SiZE
50ZH
(IN.)
1500
1600
1700
1800
1900
2000
2100
2200
2300
030-042
24 x 24
0.14
0.15
048,060
24 x 30
0.10
0.11
0.12
0.13
0.14
0.15
0.18
0.17
0.18
insulation,
wiring
or air filter(s).
For best results,
spray
outdoor-
coil fins from inside to outside
the unit. On units with an outer and
inner outdoor
coil, be sure 1o clean between
the coils. Be sure to
flush all dirt and debris from
the unit base.
Inspect
the drain pan and condensate
drain line when
inspecting
the coils. Clean the drain pan and condensate
drain by removing
all
lk_reign matter
from
the pan. Flush
the pan and drain
tube
with
clear
water. Do not splash
water on the insulation,
motor,
wiring,

Hide quick links: