The ability to properly perlbrn_ maintenance
on this equip-
ment requires certain expertise, mechanical skills, tools and
equipment. If you do not possess these, do not attempt to
perlbrn_ any maintenance on this equipment, other than those
procedures recommended
in the User's Manual. FAILURE
TO HEED THIS WARNING COULD RESULT IN SERI-
OtIS 1NJURY, DEATH OR DAMAGE TO THIS EQUIP-
MENT.
The minilnum maintenance requirements %r this equipment are as
lollows:
1. Inspect
air
filter(s)
each
month.
Clean
or replace
when
necessary.
2. Inspect
indoor
coil, outdoor
coil, drain
pan, and condensate
drain each cooling
and heating
season
lbr cleanliness.
Clean
when necessary.
3. Inspect
blower
motor
and wheel lot cleanliness
each cooling
and heating
season.
Clean
when
necessary.
For l]rst heating
season,
inspect
blower
wheel bimonthly
to determine
proper
cleaning
[?'equency.
4. Check
electrical
connections
lbr tightness
and controls
lk_r
proper
operation
each cooling
season.
Service
when
neces-
sary.
5. Check
the
drain
channel
ilk the
top cover
periodically
%r
blockage
(leaves,
insects).
Clean
as needed.
Failure to lollow these warnings could result in serious injury
or death:
1. Turn off electrical power to the unit and install lockout tag
beli_re perlorming any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts. As
with any mechanical equipment, personal injury can result
15"oresharp edges, etc.
3. Never place anything combustible either on, or ilkcontact
with, the unit.
Step 1--Air
Filter
NOTE:
Never operate the unit without a suitable air lilter ilkthe
return-air duct system. Always replace the l]lter with the same size
as originally installed. See Table 1 lor recommended
filter sizes
Inspect
air filter(s)
at least once each
month
and replace
(throwaway-type)
or clean (cleanable-type)
at least twice during
each cooling season or whenever the filters become clogged with
dust and lint.
Replace filters with the same dimensional
size and type as
originally provided, when necessary.
Step 2--Unit
Top Removal
(Outdoor-Coil
Side)
NOTE:
When perli}rming maintenance or service procedures that
require removal of the unit top, be sure to per%rm all of the routine
maintenance
procedures that require top removal, including coil
inspection and cleaning, and condensate drain pan inspection and
cleaning.
Disconnect
and tag electrical
power to the unit belk}re
removing top. Failure to adhere to this warning could cause
serious injury or death.
Only qualified service personnel should perlorm maintenance and
service procedures that require unit top removah
Reli:r to the lbllowing top removal procedures:
1. Remove 7 screws on unit top cover surface. (Save all screws.)
2. Remove 2 screws on unit top cover flange. (Save all screws.)
3. Lift top l?'om unit carefully. Set top on edge and make sum
that top is supported by unit side that is opposite duct (or
plennm) side.
4. Carefully replace and secure unit top to uniL using screws
removed ilk steps 1 and 2 above, when maintenance
and/or
service procedures are completed.
Step 3--indoor
Blower and Motor
For hmger lili:, operating economy,
and continuing
efficiency,
clean accunmlated
dirt and grease l?'om the blower wheel and
motor annually.
Disconnect
and tag electrical
power to the unit bel_re
cleaning the blower wheel. Faihn'e to adhere to this warning
could cause serious injury or death.
To clean the blower wheel:
1. Access the blower assembly as lollows:
a. Remove top access panel.
b. Remove 3 screws that hold blower orifice ring to blower
housing. Save screws.
c. Loosen setscrew(s) which secure wheel to motor shaft.
2. Remove and clean blower wheel as lollows:
m E:: ::ikt:i:Kt=Kt :
41
j
I_
___
._
I
.
---I.T.$.g..£,,,W
95
35
_$52=8o_-- "d:N:kt:t:taNd:t_"
:'_
_
E.
......
_
85
29
_
.
_
I_ _:::_:-:-:_7s
24
_04831LU70_=:
: .....................................
'_ ::_jZ_
65
18
CO
II
_--
I_
I
I
I
I
II
I--_
"
LLI
Q-
...
=
d=
£1-
Z
.
.....
Z
Z
....
,€
:
I0
E--
-_,
--_
45
7
_o 4d 0
:t N
::
_276
40
,
''
'
l,
,
I ,
, ,
I
,
1,
,
"
''_
207130 -:J,
lllillllllll
:::lllllllill
1
30
40
50
60
70
80
90
SUCT!ON
L!NE TEM PERATURE
(°F)
I
I
I
I
I
I
I
-1
4
10
16
21
27
32
SUCTION
LINE TEMPERATURE
(°C)
Fig. 18--Cooling
Charging
Chart--5OZH030 c°°_63
16