Table PD-41 — Supply Fan Performance WITH INLET GUIDE VANES — 90 Ton (Cont.)
Cfm
Std.
6.250
Air
RPM
BHP
RPM
27000
1416
43.47
1440
28000
1420
44.66
1444
29000
1424
45.81
1450
30000
1428
46.91
1453
31000
1434
48.20
1459
32000
1442
49.55
1464
33000
1451
51.09
1473
34000
1461
52.70
1482
35000
1471
54.27
1491
36000
1482
55.91
1503
37000
1494
57 .77
1514
38000
1505
59.46
1527
39000
1518
61.37
1540
40000
1533
63.50
1552
41000
1547
65.62
1566
42000
1561
67 .70
1580
43000
1576
69.89
1593
44000
1591
72.20
1609
45000
1607
74.63
1625
Notes:
1. Shaded areas indicate non-standard BHP or RPM selections. Contact your local Trane representive for more information.
2. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component
3. Maximum static pressure leaving the rooftop is 4.0'' H20 positive. The static pressure drops from the supply fan to the space cannot exceed 4.0'' H20.
4. Minimum motor horsepower is 30 hp.
5. See RT-EB-104 for further details.
Figure PD-10— Supply Fan Performance WITH INLET GUIDE VANES — 90 Ton
9
8
7
6
5
4
3
2
1
0
0
10000
Note:
1. Important: Maximum static pressure leaving the rooftop is 4.0" H
RT-PRC010-EN
Performance
Data
6.500
6.750
BHP
RPM
BHP
RPM
45.34
1467
47.44
1492
46.52
1472
48.74
1497
47.90
1474
49.87
1499
49.00
1479
51.22
1503
50.30
1484
52.52
1508
51.55
1489
53.77
1512
53.11
1496
55.23
1518
54.63
1506
56.90
1527
56.22
1515
58.53
1536
58.03
1523
60.10
1544
59.79
1534
61.91
1555
61.78
1547
63.94
1568
63.74
1560
65.94
1579
65.66
1572
67.90
1592
67.82
1585
69.97
1603
69.96
1598
72.15
1617
72.06
1613
74.46
1630
74.43
1628
76.89
1645
76.92
1643
79.30
20000
30000
40000
CFM
O positive. The static pressure drops from the supply fan to the space cannot exceed 4.0" H