Table PD-39 — Supply Fan Performance WITH INLET VANES — 60, 70 and 75 Tons
Cfm
Std
.250
Air
RPM
BHP
RPM
14000
316
1.77
382
15000
330
2.07
390
16000
344
2.41
401
17000
359
2.80
413
18000
374
3.24
425
19000
390
3.72
437
20000
405
4.24
450
21000
420
4.81
464
22000
436
5.44
478
23000
452
6.11
492
24000
468
6.85
507
25000
484
7.64
522
26000
500
8.49
538
27000
516
9.41
553
Cfm
Std
2.250
Air
RPM
BHP
RPM
14000
729
10.76
762
15000
736
11.39
770
16000
743
12.07
777
17000
750
12.80
784
18000
756
13.53
791
19000
761
14.25
797
20000
766
14.93
802
21000
771
15.60
807
22000
775
16.31
812
23000
780
17.11
816
24000
785
18.00
821
25000
789
18.94
826
26000
794
19.91
830
27000
797
20.85
835
Cfm
Std
4.250
Air
RPM
BHP
RPM
14000
956
21.90
980
15000
966
23.07
989
16000
975
24.24
999
17000
983
25.38
1008
18000
992
26.51
1016
19000
1000
27.64
1024
20000
1007
28.82
1032
21000
1014
30.05
1039
22000
1021
31.35
1046
23000
1028
32.71
1053
24000
1034
34.10
1060
25000
1040
35.49
1066
26000
1046
36.83
1072
27000
1051
38.12
1077
Notes:
1. Fan performance for 60, 70 and 75 ton rooftops are identical. Contact your local Trane representative for information on non-standard motors.
2. Shaded areas at table extremes note non-standard Bhp or Rpm selection. Contact your local Trane representative for more information.
3. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component