Table PD-33 — Supply Fan Performance WITH INLET VANES — 20 and 25 Tons
Cfm
Std
,250
Air
RPM
BHP
RPM
4000
387
.37
514
5000
420
.55
530
6000
469
.82
557
7000
526
1.21
591
8000
586
1.72
638
9000
647
2.37
692
10000
708
3.15
750
11000
769
4.10
809
Cfm
Std
2.250
Air
RPM
BHP
RPM
4000
1037
3.61
1087
5000
1056
4.12
1109
6000
1067
4.60
1122
7000
1076
5.14
1131
8000
1086
5.82
1140
9000
1095
6.56
1151
10000
1109
7.43
1160
11000
1136
8.54
1181
Cfm
Std
4.250
Air
RPM
BHP
RPM
4000
1380
7.82
1416
5000
1412
8.85
1449
6000
1436
9.85
1474
7000
1453
10.80
1493
8000
1465
11.71
1505
9000
1473
12.68
1514
10000
1482
13.79
1522
11000
1493
15.10
1533
Notes:
1. Fan performance for 20 and 25 ton rooftops is identical. However, note maximum motor hp size for each size. Contact your local Trane representative for information on
oversized motors.
2. Shaded areas at table extremes note non-standard Bhp or Rpm selection. Contact your local Trane representative for more information.
3. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component