Auxillary Circuit Breaker; Electrical Work - Samsung AS07A5(A6)MA Owner's Instructions & Installation Manual

Split-type room air conditioner (cool)
Hide thumbs Also See for AS07A5(A6)MA:
Table of Contents

Advertisement

I
O
U
NSTALLING THE
UTDOOR
NIT
Auxiliary Circuit Breaker
Outdoor unit
Auxiliary
power s/w
The designs and shape are subject to
change according to the model.

Electrical Work

38
E-
Auxiliary circuit breaker should be installed near outdoor unit so
that each access is possible. Main/outdoor power supply cable are
Distribution
board
connected to upper/lower terminal of auxiliary circuit breaker.
It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power S/W and the outdoor
unit. (the conduit kit is optional)
1
The supply voltage must be the same as the rated voltage of the
air conditioner.
2
Prepare the power souce for exclusive use with the air conditioner.
3
Use 15 amperes time delay fuse or circuit breaker.
MODEL
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
MODEL
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
Otherwise, the shot circuit in the NFB may occur.
AS07A5(A6)MA
AS09A5(A6)MA
115V~/60Hz
Single phase
6.4
32A
680W
AS12AA(AB)MC
AS18A5(A6)RC AS18A9(A0)RCD AS24A1(A2)RC
208-230V~/60Hz
208-230V~/60Hz
Single phase
Single phase
4G AWG 16
5G AWG 16
8.6A
5.4
31A
35A
1230W
1900W
AS12A5(A6)MC
115V~/60Hz
208-230V~/60Hz
Single phase
Single phase
3G AWG 14
4G AWG 16
8.5
47A
31A
900W
1320W
208-230V~/60Hz
208-230V~/60Hz
Single phase
Single phase
3G AWG 14
6G AWG 16
8.0A
37A
1770W
6.1
10.5A
10.5A
2350W