I
O
U
NSTALLING THE
UTDOOR
NIT
Auxiliary Circuit Breaker
Outdoor unit
Distribution
Auxiliary
power s/w
Electrical Work
40
E-
Auxiliary circuit breaker should be installed near outdoor unit so
that each access is possible. Main/outdoor power supply cable are
board
connected to upper/lower terminal of auxiliary circuit breaker.
It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power S/W and the outdoor
unit. (the conduit kit is optional)
1
The supply voltage must be the same as the rated voltage of the
air conditioner.
2
Prepare the power souce for exclusive use with the air conditioner.
3
Use 15 amperes time delay fuse or circuit breaker.
Power supply
Power cable
Assembly cable
Operating current(C/H)
Starting Current
Power consumption (C/H)
When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
Otherwise, the shot circuit in the NFB may occur.
MODEL
AQ30
BC
208-230V~/60Hz
Single phase
3G AWG 12
5G AWG 14 + 2G AWG 18
14A / 14A
80A
3100W / 3100W