Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in
Table
32.
Fault Condition
No Fault
n/a
Force Fault
EF0
Network Link Down
BUS ERROR
Network Failure
BUS ERROR
Default MAC Address
None
No IP Address
None
No Station Name
None
Config Error
None
Init. Failure
None
Permanent
BUS ERROR
Communication Loss
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued fault reset and upon
power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.
Option Compatibility
A limited number of options may be simultaneously connected to the drive depending on the type of option. Refer to
Table 33
for more information. More details can be found in the Options and Peripheral Devices chapter of the drive
Technical Manual.
Option
SI-C3, SI-N3, SI-P3, SI-S3, SI-EP3, SI-EN3, SI-EM3
PG-B3, PG-X3
DO-A3, AO-A3, AI-A3, DI-A3
<1> When installed in CN5-A, the AI-A3 and DI-A3 options can be used to set the frequency reference or replace the drive analog inputs with higher
resolution. When installed in CN5-B or CN5-C, these options can only be used for monitoring; their input levels will be displayed in U1-17 or
U1-21 to U1-23.
<2> Use the CN5-C connector when connecting only one option to the drive; use both CN5-B and CN5-C when connecting two options.
YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual
Table 32 Option Fault Monitor Descriptions
Status Value
Fault Declared
(U6-98/U6-99)
0
3
1300
1301
1303
1304
1305
1306
1307
1308
Table 33 Option Installation Compatibility
<1>
No faults.
Network sent a message to force this node to the fault state.
No network link to option board.
Connection with PLC Timeout.
Factory default MAC Address programmed into the option. Return for
reprogramming.
No IP Address has been programmed into the option.
No Station Name has been programmed into the option.
Configuration error on power-up.
Initialize error on power-up.
Fatal error in MAC/PHY hardware, requires power cycle to recover.
Connector
CN5-A
CN5-B, C
CN5-A, B, C
10 Troubleshooting
Description
Number of Possible Options
1
2
<2>
1
55