9. Insert guide rail
10.Tilt the fan/battery module upwards until the front latch
9.5

Cleaning

NOTICE
Damage caused by aggressive cleaning agents
Aggressive chemical agents can damage the electronics. This can result in malfunction.
Never use any type of chemical agent or liquid.
● Only remove severe dirt and contamination after prior consultation with service experts for
Use a dry, clean, lint-free ESD cleaning cloth. Wipe all external parts of the rack with it. Make
sure that the dirt is not distributed, but actually removed by constant changes of the wiping
surface of the cloth. For significant levels of pollution and dirt, use an ESD cloth soaked in ethyl
alcohol (however, not so much that it drips from the cloth).
SINAMICS SL150 6SL39616RC100AA02
Operating Instructions Rev.201910281458 EXAMPLE
back into the recesses at the lower side of the Control Unit.
Note
Only replace the fan/battery module when disconnected from the line supply (POWER
OFF).
Replace the battery at least every 3 years, and whenever the warning level is reached. If
you replace the battery too late, then this means that the retained data will be lost!
the particular product.
Maintenance
9.5 Cleaning
snaps into place.